venting installation | WDV Series Gas Fireplace |
|
|
termination clearances for buildings with combustible and noncombustible exteriors
G G=6" (152mm)
V
Combustible – 6" (152 mm)
Noncombustible – 2" (51 mm)
Inside Corner
G
V
G = Combustible 24"(610mm) Noncombustible 18"(457mm)
V
F F=6" (152mm)
Outside Corner
H |
V |
J |
Combustible & |
Noncombustible |
H = 24" (610mm) |
J = 20" (508mm) |
| D |
C | C |
|
V
E
C = Maximum depth of 48" (1219mm) for alcove location
D = Minimum width for back wall of alcove location Combustible - 38" (965mm) Noncombustible - 24" (610mm)
E = Clearance from corner in alcove location
Combustible - 6" (152mm)
Noncombustible - 2" (51mm)
| Balcony with No Side Wall | Balcony with Perpendicular |
|
|
| Alcove Location |
| |
Figure 9 - | Side Wall | 40 |
|
|
|
| ||
Allowable Venting Chart |
|
|
|
|
|
| ||
|
|
|
| 38 |
|
|
|
|
|
|
| Feet | 36 |
|
| CenteroftheHorizontalVentPipe | VerticalDimensionFromtheFloorofUnit |
How To Use The Vent Graph |
| 34 |
|
| ||||
The Vent Graph should be read in conjunction with the | in | 32 |
|
|
|
| ||
Dimensions | 30 |
|
|
|
| |||
following vent installation instructions to determine the |
|
|
|
| ||||
|
|
|
|
| ||||
relationship between the vertical and horizontal dimensions |
| 28 |
|
|
|
| ||
of the vent system. |
|
| 26 |
|
|
|
| |
1. Determine the height of the center of the horizontal vent |
| 24 |
|
|
|
| ||
| pipe exiting through the outer wall. Using this dimen- |
| 22 |
|
|
|
| |
| sion on the Sidewall Vent Graph below, locate the point |
| 20 |
|
|
|
| |
| intersecting with the slanted graph line. |
| 50" | 18 |
|
| eg: A |
|
2. | From the point of this intersection, draw a vertical line | 16 |
|
|
| |||
From Floor to |
|
|
| |||||
| to the bottom of the graph. |
| Center | 14 |
|
|
|
|
3. | Select the indicated dimension, and position the fire- |
| 12 |
|
|
|
| |
| place in accordance with same. |
|
| 10 |
|
|
| to |
| Example: If the vertical dimension from the floor of the |
| 8 |
|
|
| ||
|
|
|
|
| the | |||
| fireplace is 11' (3.4 m) the horizontal run to the face of |
| 6 |
|
|
| ||
|
|
|
|
|
| |||
| the outer wall must not exceed 16' (4.9 m). |
| 4 |
|
|
|
| |
Sidewall Vent Graph showing the relationship between |
| 2 |
|
|
|
| ||
vertical and horizontal dimensions for a Direct Vent flue |
| 2 | 4 | 6 | 8 10 1214 16 1820 |
| ||
system. |
|
|
| |||||
| Horizontal dimension from the finished outside | |||||||
|
|
| ||||||
|
| Figure 10 - | wall to the center of the pipe on the fireplace | |||||
|
| Rear Wall Venting Graph |
|
|
|
|
78D0011 | 13 |