Multiquip DCA-150SSKII Single Phase 480V, 440V, or 416 Volt, Phase, 480V, 440V, or 416 Volt

Models: DCA-150SSKII

1 92
Download 92 pages 7.3 Kb
Page 37
Image 37
Single Phase: 480V, 440V, or 416 Volt

Table of Contents

DCA-150SSKII — OUTPUTTERMINAL PANEL OVERVIEW

Voltage Selector Switch- 3 Phase 480/277V Position The following are additional voltages available when the voltage selector switch is in the 3 phase 480/277V position. (See figure 24 below.)

Single Phase: 480V, 440V, or 416 Volt

The following connection, with the voltage selector switch locked into the 3 phase 480/277V position (See Figure 24), can offer SINGLE PHASE power at 480V, 440V, or 416V.

After hooking up the hard wires to the lugs as shown in figure 27 below, 480V will be the voltage with the Voltage Regulator Knob turned toward maximum. 440 volt will be reached when the Voltage Regulator Knob is turned down, and 416 volt when the Voltage Regulator Knob is toward the lowest setting (See Figure 25).

FIGURE 25. Voltage

Regulator Knob Located

on the Control Panel.

FIGURE 24. Voltage Selector Switch 480/277V Single Phase

FIGURE 27. Hard Wire Hook-up for Single Phase 480V, 440V,

Position

or 416V

 

3 Phase, 480V, 440V, or 416 Volt

The following connection, with the voltage selector switch locked into the 3 phase 480/277V position (See Figure 24), can offer THREE PHASE power at 480V, 440V, or 416V.

After hooking up the hard wires to the lugs as shown in figure 26 below, 480V will be the voltage with the Voltage Regulator Knob turned toward maximum. 440 volt will be reached when the Voltage Regulator Knob is turned down, and 416 volt when the Voltage Regulator Knob is toward the lowest setting (See Figure 25).

Single Phase: 277V, 254V, or 240V

The following connection, with the voltage selector switch locked into the 3 phase 480/277V position (See Figure 24), can offer SINGLE PHASE power at 277V, 254V, or 240V.

After hooking up the hard wires to the lugs as shown in figure 28 below, 277V will be the voltage with the Voltage Regulator Knob turned toward maximum. 254 volt will be reached when the Voltage Regulator Knob is turned down, and 240 volt when the Voltage Regulator Knob is toward the lowest setting (See Figure 25).

FIGURE 26. Hard Wire Hook-up for Three Phase 480V, 440V,

FIGURE 28. Hard Wire Hook-up for Single Phase 277V, 254V,

or 416V

 

or 240V

DCA-150SSKII — PARTS AND OPERATION MANUAL— REV. #1 (05/08/01) — PAGE 37

Page 37
Image 37