Multiquip DCA-150SSKII - INSTALLATION, Outdoor Installation, Indoor Installation

Models: DCA-150SSKII

1 92
Download 92 pages 7.3 Kb
Page 40
Image 40
Outdoor Installation

Outdoor Installation

Install the generator in a location where it will not be exposed to rain or sunshine. Make sure that the generator is on secure level ground so it cannot slide or shift around. Also install the generator so the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture. Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear, not only to the engine parts, but also to the alternator parts.

CAUTION :

Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements. Engine exhaust must be routed to a ventilated area.

Indoor Installation

Exhaust gases from diesel engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside.The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

DO NOT cover ventilation areas on the enclosure, covering the ventilation grids will cause the engine to over heat.

Table of Contents

DCA-150SSKII — INSTALLATION

CAUTION :

An electric shock is apt to happen when vibrators are used. Pay close attention to handling when operating vibrators and always use rubber boots and gloves to insulate the body from electrical shock.

Generator Grounding

To guard against electrical shock and possible damage to the equipment, it is important to provide a good EARTH ground.

Article 250 (Grounding) of the National Electrical Code (NEC) provides guide lines for proper grounding and specifies that the cable ground shall be connected to the grounding system of the building as close to the point of cable entry as practical.

NEC articles 250-64(b) and 250-66 set the following grounding requirements:

1.Use one of the following wire types to connect the generator to earth ground.

a.Copper - 10 AWG (5.3 mm2) or larger.

b.Aluminum - 8 AWG (8.4 mm2) or larger.

2.When grounding the generator (Figure 9) connect the ground cable between the lock washer and the nut on the generator and tighten the nut fully. Connect the other end of the ground cable to earth ground.

3.NEC article 250-52(c) specifies that the earth ground rod should be buried a minimum of 8 ft. into the ground.

NOTE

When connecting the generator to any buildings electrical system ALWAYS consult with a licensed electrician.

PAGE 40 —DCA-150SSKII— PARTS AND OPERATION MANUAL — REV. #2 (05/08/01)

Page 40
Image 40
Multiquip operation manual DCA-150SSKII - INSTALLATION, Outdoor Installation, Indoor Installation, Table of Contents