Floor Protection:
When installing freestanding heater ,a floor protector must be use. Floor protection must be 3/8” minimum thickness
How to use alternate materials and how to calculate equivalent thickness.
An easy means of determining if a proposed alternate floor protector meets requirements listed in the appliance manual is to follow this procedure:
1. Convert specification to
K– factor is given with a required thickness (T) in inches:
2. Determine the
Use the formula in step (1) to convert values not expressed as “R”
For multiple layers, add
protector, the alternate is acceptable. Example:
The specified floor protector should be 3/4” thick material with a
The proposed alternate is 4” brick with a
Step (a): Use formula above to convert specification to
Step (b): Calculate R of proposed system. 4” brick of C=1.25, therefore Rbrick = 1/C = 1/1.25 =0.80 1/8” mineral board of K = 0.29, therefore Rmin.bd. =1/029 x0.125 = 0.431
Step (c): Compare proposed system R of 1.231 to specified R of 0.893. Since proposed system R is greater than required , the system is acceptable.
Definitions: |
|
|
|
|
|
Thermal conductance | = C = | Btu | = | W |
|
|
| (hr)(ft²)(°F) | (m²)(°K) |
| |
Thermal conductance | = K = (Btu)(inch) = | W = | (Btu) | ||
|
| (hr)(ft²)(°f) |
| (m)(°K) | (hr)(tf)(°F) |
Thermal conductance | = R = | (ft²)(hr)(°F) = (m²)(°K) |
| ||
|
| Btu |
| W |
|
5