B. Vertical wall exit using (6" Single Wall minimum 24 ga. blued or black pipe with elbow, and any listed 2100° UL 103 HT.

TYPE Chimney and Listed 2100° UL HT. T-Box assembly). Without optional close clearance shield and pipe shield.

Model 21 minimum clearance to combustibles.

BACK WALL

Figure 9.

B

H D FF

B

G

SIDE WALL

E

PROTECTOR

 

G

 

E

 

 

 

A

 

CC Manual backgroundManual backgroundC

A B C D E F G

MODEL 21 25” 13" 19" 15.5" 8" 3" 16"

NOTE: All clearances are to combustibles without close clearance shields and pipe shield, 6" Single Wall minimum 24 ga. blued or black pipe with elbow, and minimum floor protector.Clearances above may be reduced. Follow NFPA-211codes if available or follow instructions on (Pages 20, and 21, or Pages 24, and 25).

CEILING

SINGLE WALL

CONNECTOR

ELBOW PIPE

Figure 10.

IN

SIDE

WALL

LISTED 2100° UL 103 HT TYP.

CHIMNEY REEFER TO

MANUFACTURES INSTALLATION INSTRUCTION

LISTED 2100° UL 103 HT

TYP. CHIMNEY T-BOX

ASSEMBLY REEFER TO

MANUFACTURES

INSTALLATION

INSTRUCTION

WALL

PASS-THROUGH

CONNECTOR

17

Page 19
Image 19
New Buck Corporation installation instructions Model 21 minimum clearance to combustibles