HOW TO LOCATE CHIMNEY EXIT, AND INSTALL

Residential and Mobile Home Installation.

F. Vertical Wall Exit using (6" DVL Close Clearance Pipe, and Elbow, and any Listed 2100° UL HT chimney and Listed 2100° UL HT T-Box assembly).

With optional close clearance shield and pipe shield NOTE: For installation of of optional close clearance shields and pipe shield (See Page 33).

NOTE: For minimum clearances (See Page 25, Figure 17).

If pedestal kit is being used,and out side air is required (See Page 26).

1.Mark the plumb line on the wall directly behind the center of the heater. (See Page 25, Figure 18.)

NOTE: When using DVL Close Clearance Pipe , “maintain manufacturer’s minimum clearances" between pipe and ceiling.

2.Place the vertical portion of the heater pipe and the elbow in position and project a point onto the plumb line level with the center of the elbow.

3.Measure up so there will be at least 1/4" rise per foot of horizontal connector pipe, maintaining clearances to the ceiling as noted in (Page 25,Figure 18). This will give you the center of the hole for the chimney penetration.

4.After locating the center of the penetration, install the tee-box and chimney as per the chimney manufacturer's specifications.

5.Connect the DVL close clearance pipe to the tee-box per manufacturer’s instructions,. DVL close clearance pipe is to be connected with (3) sheet metal screws or rivets to connector collar on heater.(See Page 25,Figure 18).

24

Page 26
Image 26
New Buck Corporation 21 How To Locate Chimney Exit, And Install, Residential and Mobile Home Installation