NOTE: In addition, a connector to a masonry chimney shall extend through the wall to the inner face or liner but not beyond, and shall be firmly cemented to masonry. EXCEPTION: A thimble may be used to facilitate removal of the chimney connector for cleaning, in which case the thimble shall be permanently cemented in place with high- temperature cement.

2.Once the through-the-wall thimble codes are met, simply connect the chimney collar to the wall pass-through connector using #24 ga. minimum, blued or black steel connector pipe as follows:

(a)Maintain 1/4" rise per foot (horizontal length) from the appliance to the chimney.

(b)Connect each section so the crimped end faces downward or back toward the unit.

(c)Secure each section to each other using at least three (3) sheet metal screws or rivets.

(d)Use three (3) sheet metal screws to fasten pipe to connector collar on heater.

D. Ceiling Exit-Close Clearance

1. Suspend a plumb bob from the ceiling above the unit so that the weight is hanging in the center of the flue exit. (A small weight on a string will serve as a plumb bob.) Mark the ceiling where the string is suspended to locate the center of the chimney hole.

2.After locating the center of the hole, install the ceiling support box, chimney flashing and rain cap.

3.Now connect the stove and ceiling support box using #24 ga. minimum blued or black steel connector pipe. (DO NOT USE GALVANIZED PIPE.) Connect each section so the crimped end faces downward, and secure each section to each other using at least three (3) sheet metal screws or rivets. Next, install an optional New Buck Corporation chimney connector to the flue exit of the heater or you may use “Ell” brackets to fasten the pipe to the stove.

4.Install Single Wall Connector and chimney system per manufacturer’s written operating instructions. See manufacturer's list of tested pipes in this manual.

18

Page 20
Image 20
New Buck Corporation 85 installation instructions D. Ceiling Exit-CloseClearance