Chimney
These models are designed for connection to:
(1)Simpson Duravent - Dura Black
(2)Metal Fab
(3)Ameritec - BSR
NOTE: This Room Heater must be converted to (1) a chimney complying with the requirements for Type HT chimneys in the Standard for chimneys,
DETERMINING THE CHIMNEY LOCATION
A.Ceiling Exits: (Using 6" Single Wall Pipe and UL 103 HT type chimney system listed with manufacturer in this section of manual.)
1.Suspend a plumb bob from the ceiling above the unit so that the weight is hanging in the
center of the flue exit. (A small weight on a string will serve as a plumb bob.) Mark the ceiling where the string is suspended to locate the center of the chimney.
2.After locating the center of the hole, install the ceiling support box, chimney, flashing and rain cap per the chimney manufacturer's instructions.
3.Now connect the stove and ceiling support box using #24 ga. minimum blued or black steel connector pipe. (DO NOT USE GALVANIZED PIPE.) Connect each section so the crimped end faces downward, and secure each section to each other using at least
15