Nordyne RC 92+, RL 90+ Equipment in a Confined Space, Space with all Combustion Air drawn from

Models: RC 92+ RL 90+

1 40
Download 40 pages 28.41 Kb
Page 15
Image 15
Figure 13. Equipment in a Confined

Vent or

Chimney

Each opening to outside must be at least 1 sq. in. per 4000 Btuh of total input rating.

-

12"

 

Max

 

 

 

 

 

Furnace

-

 

 

12" Max

Water Heater

 

Minimum

 

Total Input

Free Area

Round Duct

Rating (Btuh)

(Each Opening)

Diameter

40,000

10 sq. in.

4"

60,000

15 sq. in.

5"

80,000

20 sq. in.

5"

100,000

25 sq. in.

6"

120,000

30 sq. in.

6"

140,000

35 sq. in.

7"

160,000

40 sq. in.

8"

Figure 12. Equipment in a Confined Space with all Combustion Air drawn from Out- doors through Exterior Wall

Ventilation Louvers at each end of attic

 

Vent or

 

 

Chimney

 

 

Ventilation Louvers

 

(each end of attic)

 

-

 

 

Outlet

NOTE: Air open-

 

Air

ings shall each

 

Water

have a free area

Furnace

of not less than

Heater

one square inch

 

 

 

per 4,000 Btuh of

Alternate

 

the total input rat-

Inlet Air

ing of all equipment

Air Inlet

in the enclosure.

 

-

 

 

-

-

Ventilation Louvers For

Unheated Crawl Space

Figure 14. Equipment in a Confined Space with all Combustion Air drawn from Out- doors through Ventilated Crawl Space and Ventilated Attic

Vent or

Chimney

Vent or

Figure 15. Equipment in a Confined SpaceSpace with all Combustion Air drawn fromChimney

Attic

Insulation with all Combustion Air Drawn from the

Furnace

Water Heater

Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.

Outdoors through Vertical Ducts – from Ducts must extend above attic insulation.

Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.

12" Max

Air Duct

Air Duct

must be

Furnace

at least

1 sq. in.

 

per 2000

 

Btuh of

Air Duct

total input

rating.

 

Water Heater

 

 

Minimum

 

Total Input

Free Area

Round Duct

Rating (Btuh)

(Each Opening)

Diameter

40,000

10 sq. in.

4"

60,000

15 sq. in.

5"

80,000

20 sq. in.

5"

100,000

25 sq. in.

6"

120,000

30 sq. in.

6"

140,000

35 sq. in.

7"

160,000

40 sq. in.

8"

 

Minimum

 

Total Input

Free Area

Round Duct

Rating (Btuh)

(Each Opening)

Diameter

40,000

20 sq. in.

5"

60,000

30 sq. in.

6"

80,000

40 sq. in.

7"

100,000

50 sq. in.

8"

120,000

60 sq. in.

9"

140,000

70 sq. in.

10"

160,000

80 sq. in.

10"

Figure 13. Equipment in a Confined

Figure 15. Equipment in a Confined Space

Space with all Combustion Air drawn from

with all Combustion Air Drawn from the

Outdoors through Vertical Ducts – from

Outside through Horizontal Ducts

Ventilated Attic

 

15

Page 15
Image 15
Nordyne RC 92+, RL 90+ Equipment in a Confined Space, Space with all Combustion Air drawn from, Ventilated Attic