Nordyne RL 90+ Start-Upand Adjustments, Start-UpProcedure, Verifying and Adjusting Firing Rate

Models: RC 92+ RL 90+

1 40
Download 40 pages 28.41 Kb
Page 32
Image 32
START-UP AND ADJUSTMENTS

To check the heat anticipator setting either:

1.Add the current draw of the system compo- nents; or

2.Measure the current flow on the thermostat R-W circuit after the circulating blower motor has started.

Set the heat anticipator according to the ther- mostat manufacturer’s instructions for heat anticipator settings.

START-UP AND ADJUSTMENTS

Prior to start-up, verify that:

1.The line voltage power leads are securely connected, that the polarity of the con- nections is correct, and that the furnace is properly grounded.

2.The thermostat wires (R, W, Y, and G) are securely connected to the correct leads on the terminal strip of the circuit board.

3.The gas line service pressure does not exceed 10.0 in. water column (0.36 psig), and is not less than 4.5 in. water column (0.16 psig) for natural gas. For LP gas the line service pressure must not exceed 14 in. water column (0.51 psig), and must not be less than 11.0 in. W.C. (0.40 psig).

4.The roll-out and vent safety manual reset switches are closed. If necessary, press the red button to reset a switch. See Figure 30 for location. DO NOT install a jumper wire across a switch to defeat its function. If a switch reopens on start-up, DO NOT reset the switch without identifying and correcting the fault condition which caused the switch to trip.

5.The blower door is in place, closing the door switch in the line voltage circuit.

6.The gas line has been purged and all con- nections are leak tight.

Start-Up Procedure

1.Set the thermostat to the lowest setting.

2.Close the disconnect(s) to provide line volt- age to the furnace.

3.Follow the procedures given on the operating instructions label attached to the furnace.

4.Set the thermostat above room temperature and verify the sequence of operation. (See the SEQUENCE OF OPERATION.)

5.After the furnace has run for approximately five minutes, set the thermostat below room temperature and verify steps (9) through (11) of the SEQUENCE OF OPERATION.

Verifying and Adjusting

Firing Rate

The firing rate must be verified for each installa- tion to prevent over-firing the furnace.

NOTE: The firing rate must not exceed the rate shown on the furnace rating plate. At altitudes above 2000 ft. the firing rate must be adjusted as described in the high altitude section.

Use the following procedure to determine the firing rate:

1.Shut off all other gas fired appliances.

2.Start the furnace and allow it to run for at least three minutes.

3.Measure the time (in seconds) required for the gas meter to complete one revolution.

4.Convert the time per revolution to cubic feet of gas per hour using Table 13.

5.Multiply the gas flow rate in cubic feet per hour by the heating value of the gas in Btu per cubic foot to obtain the firing rate in Btuh. Example:

Time for 1 revolution of a gas meter with a 1 cubic foot dial = 40 seconds.

From Table 9 read 90 cubic feet per hour of gas.

Heating value of the gas (obtained from gas supplier) = 1040 Btu per cubic foot.

• Firing rate = 1040 x 90 = 93,600 Btuh.

 

 

 

 

 

A/C Condensing Unit

 

 

 

 

 

 

Condensing Unit

 

 

 

 

 

 

 

Control Box

 

 

 

 

 

 

COM

 

Blower Off 6090120180

 

R

R

 

3 Amp

Timing

 

Connect

C

 

24 V

Fuse

TWIN

 

 

 

 

Y

 

 

 

 

 

R & W

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

For

G

 

 

 

 

 

 

 

 

 

 

Flame Signal Light

 

Heating

 

 

 

 

 

 

G

 

 

 

 

(Yellow)

 

Only

W

 

 

 

 

 

 

 

 

 

 

 

Room

W

 

 

 

 

Status Light

 

 

 

 

 

 

 

9

6

3

 

 

(Red)

 

Thermostat

 

 

 

 

 

 

 

 

 

8

5

2

 

 

 

 

 

 

7

4

1

 

 

 

 

NOTE: The "Y"

 

 

 

 

 

 

 

terminal on the

 

 

 

 

 

 

 

UTEC control board

 

 

 

 

 

 

 

must be connected

EAC

 

 

 

 

 

 

to the thermostat

 

 

 

 

 

 

for proper cooling

 

Neutrals

 

 

mode operation.

HUM

 

 

 

FIELD WIRING

 

 

Unused Motor Leads

 

 

6

3

M3 M2 M1 HUM

XFMR EAC COOL HEAT

 

Low Voltage

 

 

L1

 

 

5

2

Connections

 

 

 

 

 

 

4

1

 

 

 

Figure 27. Low Voltage Field,

Four-wire Heating/Cooling Applications

32

Page 32
Image 32
Nordyne RL 90+, RC 92+ Start-Upand Adjustments, Start-UpProcedure, Verifying and Adjusting Firing Rate, Low Voltage Field