VENT TERMINAL

AIR SUPPLY INLET

AREA WHERE TERMINAL IS NOT PERMITTED

 

 

 

 

 

 

 

 

 

Canadian Installations1

 

US Installations2

A =

Clearance above grade, veranda, porch,

12 inches (30 cm)

 

12 inches (30 cm)

 

deck, or balcony

 

 

 

 

 

 

 

 

B =

Clearance to window or door that may be

6 inches (15 cm) for appliances 10,000

6 inches (15 cm) for appliances 10,000

 

opened

 

Btuh (3 kW), 12 inches (30 cm) for

Btuh (3 kW), 9 inches (23 cm) for

 

 

 

appliances > 10,000 Btuh (3 kW) and

appliances > 10,000 Btuh (3 kW) and

 

 

 

100,00 Btuh (30 kW), 36 inches (91 cm)

50,000 Btuh (15 kW), 12 inches (30 cm)

 

 

 

for appliances >100,00 Btuh (30 kW)

for appliances > 50,000 Btuh (15 kW)

 

 

 

 

 

C =

Clearance to permanently closed window

*

 

*

D =

Vertical clearance to ventilated soffit

 

 

 

 

 

located above the terminal within a

 

*

 

*

 

horizontal distance of 2 feet (61 cm) from

 

 

 

 

 

 

the center line of the terminal

 

 

 

 

E =

Clearance to unventilated soffit

 

*

 

*

F =

Clearance to outside corner

 

*

 

*

G =

Clearance to inside corner

 

*

 

*

H =

Clearance to each side of center line

 

3 feet (91 cm) within a height 15 feet

*

 

extended above meter/regulator assembly

above the meter/regulator assembly

 

 

I =

Clearance to service regulator vent outlet

3 feet (1.83 m)

 

*

J =

Clearance to nonmechanical air supply inlet

6 inches (15 cm) for appliances 10,000

6 inches (15 cm) for appliances 10,000

 

to building or the combustion air inlet to any

Btuh (3 kW), 12 inches (30 cm) for

Btuh (3 kW), 9 inches (23 cm) for

 

other appliance

 

appliances > 10,000 Btuh (3 kW) and

appliances > 10,000 Btuh (3 kW) and

 

 

 

100,00 Btuh (30 kW), 36 inches (91 cm)

50,000 Btuh (15 kW), 12 inches (30 cm)

 

 

 

for appliances >100,00 Btuh (30 kW)

for appliances > 50,000 Btuh (15 kW)

 

 

 

 

 

K =

Clearance to a mechanical air supply inlet

6 feet (1.83 m)

 

3 feet (91 cm) above if within 10 feet

 

 

 

 

 

(3 m) horizontally

 

 

 

 

 

L =

Clearance above paved sidewalk or paved

7 feet (2.13 m) †

 

*

 

driveway located on public property

 

 

 

 

 

 

 

 

 

 

 

 

 

M =

Clearance under veranda, porch deck, or

12 inches (30 cm) ‡

 

*

 

balcony

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code

2In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

*For clearances not specified in ANSI Z223.1 / NFPA 54 or CSA B149.1, the following statement shall be included:

“Clearance in accordance with local installation codes, and the requirements of the gas supplier and the manufacturer’s installation instructions.”

Figure 19. Vent Termination Clearances for Direct Vent Furnaces