Nordyne RC 92+, RL 90+ Verifying and Adjusting Temperature Rise, Blower Speed Tap Location

Models: RC 92+ RL 90+

1 40
Download 40 pages 28.41 Kb
Page 33
Image 33
Verifying and Adjusting

6.Adjustments to the firing rate can be made by adjusting the gas manifold pressure. See the High Altitude Application section for additional information of firing rate at elevations above 2000 ft.

The manifold pressure must be set to the ap- propriate value for your installation. Refer to either Table 8 for natural gas or Table 9 for LP/propane gas to verify the manifold pressure setting required for your particular installation.To adjust the manifold pressure, remove the regula- tor cap and turn the adjusting screw clockwise to increase pressure or counterclockwise to reduce pressure. Replace the regulator cap after adjustments are complete.

!CAUTION:

Do not re-drill the burner orifices. If the orifice size must be changed, use only new orifices.

Verifying and Adjusting

Temperature Rise

Verify that the temperature rise through the furnace is within the range specified on the furnace rating plate. Temperature rises outside the specified range could result in premature heat exchanger failure.

Place thermometers in the return and supply air stream as close to the furnace as possible. The thermometer on the supply air side must be shielded from direct radiation from the heat exchanger to avoid false readings. Adjust all registers and duct dampers to the desired position and run the furnace for fifteen minutes before taking any temperature readings. The temperature rise is the difference between the supply and return air temperatures.

For typical duct systems, the temperature rise will fall within the range specified on the rat- ing plate with the blower speed at the factory recommended setting. If the temperature rise measured is outside the range specified, it may be necessary to change the blower speed.Lower blower speeds will increase the temperature rise and higher blower speeds will decrease the temperature rise.

The furnace is equipped with a multispeed motor. Heating and cooling speed selection is made by moving the leads on the integrated control board located in the furnace. The wiring diagram on the furnace and Figures 27, 28 and 29 show the speed taps for adjusting motor speed.

If it is desired that the blower operate at the same speed for heating and cooling, tape off the terminal of the unused blower wire. Install the jumper wire, found in the plastic instruction bag, across the HEAT and COOL taps on the

 

R

 

C

 

Y

 

G

 

W

Common

 

Leads

EAC

Connect

HUM

Neutral

 

Lead of

 

Electronic

 

Air Cleaner

 

and/or Humidifier

 

Here.

 

COM

24 V

9

6

3

8

5

2

7

4

1

Neutrals

6 3

52

41

3 Amp Fuse

Unused Motor

Leads

 

 

 

 

 

 

 

HUM

 

M1

M2

M3

 

 

 

Flame Signal

Light (Yellow)

Status

Light (Red)

HEAT

COOL

EAC

XFMR

L1

Figure 28. Blower Speed Tap Location Electronic Air Tap (.5A@ 120 VAC)

Humidifier Tap

Heating

(.5A@ 120 VAC)

Speed Tap

Cooling Speed Tap

Figure 28. Blower Speed Tap Location

33

Page 33
Image 33
Nordyne RC 92+, RL 90+ installation instructions Verifying and Adjusting Temperature Rise, Blower Speed Tap Location