(b)For direct-vent appliances, mechanical- vent heating appliances or domestic hot water equipment where the bottom of the vent terminal and the air intake is installed above four feet above grade the following requirements must be satisfied:

1.If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detec- tor and alarm shall be placed in the liv- ing area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).

2.A carbon monoxide detector shall:

a.Be located in the room that houses the appliance or equipment;

b.Be either hard-wired or battery pow- ered or both; and

c.Shall comply with NFPA 720 (2005 Edition).

3.A Product-approved vent terminal must be used, and if applicable, a Product- approved air intake must be used. In- stallation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.

This furnace is certified for use on wood flooring. The furnace must be installed on a solid surface and must be level front to back and side to side. This furnace must not be installed directly on carpeting, tile, or any combustible material other than wood flooring.

DOWNFLOW WARNING (*RL Models):

The design of the downflow furnace is certified for natural or propane gas and for installation on non-combustible flooring. A special combustible floor sub-base is required when installing on a combustible floor. Failure to install the sub-base may result in fire, property damage and personal injury. The special downflow sub-bases are fac- tory supplied accessories, part number 902974, 902677, 904108 and 904165. Part #904108 is an adjustable sub-base kit and it can be used on all cabinet sizes. When the furnace is installed on a factory or site-built cased air conditioning coil, the sub-base is not necessary. However, the plenum attached to the coil casing must be installed such that its surfaces are at least 1” from combustible construction.

A gas-fired furnace installed in a residential ga- rage must be installed so that the burners and the ignition source are located a minimum of 18” from the floor.The furnace must be located or protected to avoid physical damage by vehicles.

Location

The furnace must be installed on a level surface, and as close to the center of the air distribution system as possible. See Table 3 for overall di- mensions to determine the required clearances in hallways, doorways, stairs, etc. to allow the furnace to be moved to the installation point.The furnace must be installed so that all electrical components are protected from water.

Minimum clearances to combustible materials are listed in Table 4. Access for positioning and servicing must be considered when locating the unit. Twenty four inches is the minimum required clearance for servicing the unit. Thirty inches is the minimum required clearance for positioning the unit. Thirty six inches is the recommended clearance from the front of the unit. Please note that a panel or door can be located such that the minimum clearance on the rating plate is satis- fied, but that panel or door must be removable and allow the appropriate clearance for your installation.

HORIZONTAL INSTALLATIONS

The upflow model furnaces are approved for horizontal installation. Installation Kit #903568 is available for horizontal applications. The parts may also be field supplied. NOTE: Down- flow models are NOT approved for horizontal installation.

!CAUTION:

Damage to the product resulting from failure to follow instructions or use of unauthorized parts may void the manufacturer’s product warranty coverage.

The 90+ upflow furnace can be installed hori- zontally in an attic, basement, crawl space or alcove.This furnace can be installed horizontally to the clearances listed in Table 4 on a platform

10

Page 10
Image 10
Nordyne RL 90+, RC 92+ installation instructions Downflow Warning *RL Models, Location, Horizontal Installations