(b)For
1.If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detec- tor and alarm shall be placed in the liv- ing area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).
2.A carbon monoxide detector shall:
a.Be located in the room that houses the appliance or equipment;
b.Be either
c.Shall comply with NFPA 720 (2005 Edition).
3.A
This furnace is certified for use on wood flooring. The furnace must be installed on a solid surface and must be level front to back and side to side. This furnace must not be installed directly on carpeting, tile, or any combustible material other than wood flooring.
DOWNFLOW WARNING (*RL Models):
The design of the downflow furnace is certified for natural or propane gas and for installation on
A
Location
The furnace must be installed on a level surface, and as close to the center of the air distribution system as possible. See Table 3 for overall di- mensions to determine the required clearances in hallways, doorways, stairs, etc. to allow the furnace to be moved to the installation point.The furnace must be installed so that all electrical components are protected from water.
Minimum clearances to combustible materials are listed in Table 4. Access for positioning and servicing must be considered when locating the unit. Twenty four inches is the minimum required clearance for servicing the unit. Thirty inches is the minimum required clearance for positioning the unit. Thirty six inches is the recommended clearance from the front of the unit. Please note that a panel or door can be located such that the minimum clearance on the rating plate is satis- fied, but that panel or door must be removable and allow the appropriate clearance for your installation.
HORIZONTAL INSTALLATIONS
The upflow model furnaces are approved for horizontal installation. Installation Kit #903568 is available for horizontal applications. The parts may also be field supplied. NOTE: Down- flow models are NOT approved for horizontal installation.
!CAUTION:
Damage to the product resulting from failure to follow instructions or use of unauthorized parts may void the manufacturer’s product warranty coverage.
The 90+ upflow furnace can be installed hori- zontally in an attic, basement, crawl space or alcove.This furnace can be installed horizontally to the clearances listed in Table 4 on a platform
10