WARN(ING) Screens

All warning screens read status as “No” under normal conditions. If the appropriate condition is met, that screen will change to “Yes.”

acin freq too high: AC source is above 66 Hz (upper limit) and will be dropped

acin freq too low: AC source is under 54 Hz (lower limit) and will be dropped

acin voltage too high: AC source’s voltage is over 140 Vac (default limit) and will be dropped

acin voltage too low: AC source’s voltage is under 108 Vac (default limit) and will be dropped

acin input current exceeds max: AC loads are drawing more current than the rating of the FX allows

temperature sensor fault: an internal FX temperature sensor is malfunctioning

internal comm error detected: there is a communication problem between MATE and Inverter (see p. 23)

internal fan failure detected: the Inverter’s internal cooling fan is not operating properly

The following items are not warnings, but are data readings related to the temp sensor warning

airtemp: displays a numeric value representing the air temperature around the Inverter

fettemp: displays a numeric value representing the temperature of the FETs (Field Effect Transistors)

captemp: displays a numeric value representing the temperature of the ripple capacitors

(These values are used for troubleshooting purposes. The higher the numerical value, the cooler the temperature.)

Status Discon(nect) Screens

STATUS/FX/PAGE2------------------

STATUS/FX/PAGE2-----------------

choose category:

choose category:

 

PG1 ERROR WARN PG3

PG2 DISCON

SELL MAIN

Pressing the <PG3> soft key brings up more STATUS categories.

Pressing the <DISCON> soft key brings up the first DISCON screen.

Pressing the <DOWN> soft key brings up successive DISCON screens.

STATUS/FX/DISCON-----------

P00

STATUS/FX/DISCON----------

P00

STATUS/FX/DISCON-----------

P00

acin freq

 

No

acin freq

 

 

No

acin voltage

 

No

too high

 

 

too low

 

 

 

> max

 

 

 

DOWN

STATUS

PORT

DOWN

UP

TOP

PORT

DOWN

UP

TOP

PORT

STATUS/FX/DISCON-----------

P00

STATUS/FX/DISCON----------------

STATUS/FX/PAGE2----------------

acin voltage

 

No

end of DISCON menu

choose category:

< min

 

 

 

 

 

DOWN

UP TOP

PORT

UP

TOP STATUS

PG2 DISCON SELL MAIN

Push <TOP> to return to the first ERROR screen.

Push <STATUS> to return to the “choose category” STATUS /FX/PAGE2 screen.

Push <MAIN> to return to the Main screen.

DISCON(NECT) Screens

acin freq too high: displays “Yes” if the AC source exceeds 66 Hz and the Inverter disconnects from the source

acin freq too low: displays “Yes” if the Inverter disconnects from an AC source below 54 Hz

acin voltage > max: the source of the AC voltage exceeds the Inverter maximum of 140 Vac

acin voltage < min: the source of the AC voltage falls below the Inverter minimum of 108 Vac

31

Page 33
Image 33
Outback Power Systems OBX-IC2024S-120/60 owner manual Status Disconnect Screens