OBX-IC2024S-120/60 Inverter/Charger Specifications
Nominal DC Input Voltage Range | 24 Vdc |
Nominal AC Voltage / Frequency | 120 Vac / 60 Hz |
Continuous Power Rating at 25°C Ambient | 2000 VA |
Continuous AC RMS Output at 25°C | 16.7 Aac |
|
|
Idle Power - Full AC Output | ≈ 20 watts |
|
|
Idle Power - Search Mode | 6 watts |
Typical Efficiency | 92% |
Total Harmonic Distortion - Typical | 2% |
Output Voltage Regulation | ± 2% |
Maximum Output Current – Peak (1 mSec) | 70 Aac |
Maximum Output Current - RMS (100 mSec) | 50 Aac |
AC Overload Capability - Surge | 6000 VA |
AC Overload Capability - 5 Second | 4800 VA |
AC Overload Capability - 30 Minutes | 3200 VA |
AC Input Current Maximum | 30 Aac |
AC Input Voltage Range | 80 to 150 Vac |
|
|
AC Input Frequency Range | 54.0 to 66.0 Hz |
DC Input Range | 21.0 to 34.0 Vdc |
DC Input Current – Rated Power | 100 Adc |
|
|
Maximum DC Input Surge Current | 300 Adc |
Continuous Battery Charger Output | 55 Adc |
Recommended DC Voltage Range
24V Systems
21 – 34 Vdc
Maximum DC Input Current
Note: This is the maximum DC current the Inverter will draw from the battery when starting very large AC loads. It is not used for sizing the DC disconnect or selecting DC cable gauge. It is used to select the minimum reasonable battery capacity.
300 Adc
Rated DC Input Current
Note: This is the maximum continuous DC current that the Inverter will draw from the batteries when inverting.
100 Adc