INVERTER DEFAULT VALUES (subject to change with upgrades)

24 VDC System

DEFAULT

MINIMUM

MAXIMUM

Float Voltage

27.4 Vdc

24 Vdc

30 Vdc

Absorb Voltage

29.4 Vdc

26 Vdc

32 Vdc

EQ Voltage

28.8 V

28 Vdc

34 Vdc

ReFloat

25 Vdc

22 Vdc

26 Vdc

LBCO

21 Vdc

18 Vdc

24 Vdc

Absorb Time

2.0 hours

0.0 hours

24.0 hours

EQ Time

1.0 hours

0.0 hours

24.0 hours

Float Time

1.0 hours

0.0 hours

24.0 hours

Charger Draw

5 Aac

0 Aac

7 Aac

AC1/Grid Transfer Delay

6 AC cycles

0 AC cycles

240 AC cycles

AC2/Gen Transfer Delay

60 AC cycles

0 AC cycles

240 AC cycles

 

 

 

 

Grid Lower Limit

108 Vac

40 Vac

115 Vac

Grid Upper Limit

140 Vac

130 Vac

150 Vac

Grid Connect Delay

0.5 min

0.2 min

15.0 min

Gen Lower Limit

108 Vac

40 Vac

115 Vac

Gen Upper Limit

140 Vac

130 Vac

150 Vac

 

 

 

 

AC DROP or USE

USE

N/A

N/A

Charger OFF/AUTO/ON

AUTO

N/A

N/A

 

 

 

 

Search Threshold

6 watts

0 watts

50 watts

Search Pulses

8

2

20

Search Pulse Spacing

60 AC cycles

4 AC cycles

120 AC cycles

Stacking Phase

1 or 2 phase

N/A

N/A

InPut Select

Gen

N/A

N/A

Grid Input Settings

28 Aac

5 Aac

30 Aac

Gen Input Settings

28 Aac

2 Aac

30 Aac

Set Output Voltage

120 Vac

115 Vac

125 Vac