< Cooling Capacity >

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RATING CAPACITY:

18,300 BTU/h

 

AIR FLOW RATE:

706 CFM

 

INDOOR

 

 

 

 

OUTDOOR

 

 

 

 

 

ENT. TEMP. o F (o C)

 

 

AMBIENT TEMP. o F (o C)

 

 

 

WB

 

DB

 

65

75

85

 

95

105

115

 

 

 

 

 

(18.3)

(23.9)

(29.4)

 

(35.0)

(40.6)

(46.1)

 

 

 

 

TC

18,370

17,750

17,080

 

16,550

15,760

14,900

 

 

72

(22.2)

SHC

15,040

14,770

14,490

 

14,220

13,940

13,530

 

59

76

(24.4)

SHC

17,370

17,100

16,820

 

16,550

15,760

14,900

 

(15.0)

80

(26.7)

SHC

18,370

17,750

17,080

 

16,550

15,760

14,900

 

 

84

(28.9)

SHC

18,370

17,750

17,080

 

16,550

15,760

14,900

 

 

88

(31.1)

SHC

18,370

17,750

17,080

 

16,550

15,760

14,900

 

 

 

 

TC

19,260

18,620

17,930

 

17,410

16,590

15,710

 

 

72

(22.2)

SHC

12,430

12,160

11,890

 

11,610

11,340

10,930

 

63

76

(24.4)

SHC

14,770

14,490

14,220

 

13,940

13,670

13,260

 

(17.2)

80

(26.7)

SHC

17,230

16,960

16,690

 

16,410

16,140

15,710

 

 

84

(28.9)

SHC

19,260

18,620

17,930

 

17,410

16,590

15,710

 

 

88

(31.1)

SHC

19,260

18,620

17,930

 

17,410

16,590

15,710

 

 

 

 

TC

20,150

19,500

18,800

 

#

18,300

17,450

16,540

 

 

72

(22.2)

SHC

9,830

9,550

9,280

 

9,140

8,730

8,460

 

67

76

(24.4)

SHC

12,160

11,890

11,610

 

11,470

11,060

10,790

 

(19.4)

80

(26.7)

SHC

14,630

14,350

14,080

 

13,810

13,530

13,260

 

 

84

(28.9)

SHC

16,960

16,690

16,410

 

16,270

15,860

15,590

 

 

88

(31.1)

SHC

19,290

19,020

18,740

 

18,300

17,450

16,540

 

 

 

 

TC

21,050

20,390

19,670

 

19,200

18,330

17,390

 

 

72

(22.2)

SHC

6,950

6,810

6,540

 

6,400

5,990

5,710

 

71

76

(24.4)

SHC

9,280

9,140

8,870

 

8,730

8,320

8,040

 

(21.7)

80

(26.7)

SHC

11,750

11,470

11,340

 

11,060

10,790

10,510

 

 

84

(28.9)

SHC

14,080

13,940

13,670

 

13,530

13,120

12,850

 

 

88

(31.1)

SHC

16,410

16,270

16,000

 

15,860

15,450

15,180

 

 

 

 

TC

21,830

21,170

20,440

 

20,010

19,120

18,040

 

75

76

(24.4)

SHC

6,540

6,400

6,120

 

5,990

5,710

5,440

 

(23.9)

80

(26.7)

SHC

9,000

8,870

8,590

 

8,460

8,180

7,910

 

 

84

(28.9)

SHC

11,340

11,200

10,930

 

10,790

10,510

10,240

 

 

88

(31.1)

SHC

13,670

13,530

13,260

 

13,120

12,850

12,570

TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)

NOTE

1.Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB

:Outdoor Ambient Temp. 95 °F (35 °C) DB

2.Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.