2. SPECIFICATIONS
2-1. Unit Specifications
Outdoor Unit
Indoor Unit
Duct Less Type Rated |
|
| < 230V > | ||||
Type |
|
|
| ||||
|
|
|
|
|
| ||
Number of Connectable Indoor Units |
|
| 3 | ||||
|
|
|
|
|
| ||
Number of Operatable Indoor Units |
|
| 3 | ||||
|
|
|
|
|
| ||
Voltage Rating |
|
|
| 230V | |||
|
|
|
|
|
|
| |
Performance |
|
|
|
|
| Cooling | |
|
|
|
|
|
| ||
Total Capacity |
|
| BTU/h | 17,000 | ( 6,800 to 18,800 ) | ||
|
|
| |||||
|
|
|
| kW | 5.00 | ( 1.90 to 5.50 ) | |
| Sensible Capacity | BTU/h |
| 14,300 | |||
| Latent Capacity | BTU/h |
| 2,700 | |||
| Air Circulation | (High) | ft3/min (m3/h) |
| 1,707 (2,900) | ||
| Available Voltage Range | V |
| 187 to 253 | |||
Rating | Running Amperes | A |
| 6.3 | |||
|
| ||||||
| Power Input |
|
| W |
| 1,420 | |
Electrical | Power Factor |
|
| % |
| 98 | |
Compressor Locked Rotor Amperes | A |
| 13.0 | ||||
| EER |
|
| BTU/h/W |
| 12.0 | |
| SEER |
|
| BTU/Wh |
| 18.0 | |
|
|
|
|
|
| ||
| Fuse or Circuit Breaker Capacity | A |
| 15 | |||
|
|
|
|
|
| Outdoor Unit | |
|
|
|
|
|
| ||
| Control |
|
|
| Microprocessor | ||
| Fan Speeds |
|
|
| Auto (Hi, Me, Lo) | ||
Features | Compressor |
|
|
| DC Twin Rotary (Inverter) | ||
Refrigerant / Amount charged at shipment | Ibs (g) | R410A / 6.17 (2,800) | |||||
| |||||||
| Refrigerant Control |
| Electric Expansion Valve | ||||
|
|
|
|
|
| ||
| Operation Sound (High) Cool |
| 50 | ||||
| Refrigerant Tubing Connections |
|
| Flare Type | |||
| Max. allowable tubing length per unit | ft (m) |
| 82 (25) | |||
| Refrigerant |
| Narrow tube | inch (mm) |
| 1/4 (6.35) × 3 | |
|
|
|
|
|
|
| |
| Tube Diameter |
| Wide tube | inch (mm) |
| 3/8 (9.52) × 3 | |
Weight |
|
|
|
|
| Outdoor Unit | |
|
|
|
|
|
| ||
| Unit Dimensions | inch | |||||
& | Height × Width × Depth | (mm) | (740 × 900 × 320) | ||||
Package Dimensions | inch | ||||||
Dimensions | |||||||
Shipping Volume | cu.ft (m3) |
| 13.41 (0.38) | ||||
| Height × Width × Depth | (mm) | (868 × 1,050 × 423) | ||||
| Weight |
| Net | Ibs (kg) |
| 138.9 (63.0) | |
|
|
| Shipping | Ibs (kg) |
| 147.7 (67.0) | |
|
|
|
|
|
|
|
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
1.The values shown in performance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Tables" in this manual.
Indoor Unit : | Outdoor Unit : |
The combination indoor unit is AHRI 210/240. |
|
2.Rating conditions are: Cooling : Indoor air temp. 80 °F DB / 67 °F WB Outdoor air temp. 95 °F DB / 75 °F WB
8