Panasonic CU-4KS31NBU 7-2-2, Low Start Current, Compressor Temperature Control, Current control

Models: CU-4KS31NBU

1 114
Download 114 pages 23.14 Kb
Page 70
Image 70
(2) Current control

(2) Current control

The operating frequency upper limits shown in the figure below are established for frequency reduction and increase-prohibit.

Current(A) Example of operation during cooling

 

Trip

Hz reduction

Hz reduction

Hz increase prohibit

Hz increase

 

 

prohibit

 

 

(16)

Hz reduction

 

Hz increase prohibit

 

(15.6)

 

 

 

0

Frequency (Hz)

 

 

(30)

7-2-2.

Low Start Current

Operation starts at (8 Hz), and the start current is less than the normal operating current. This prevents the flickering of fluorescent lights or television screens that occurs when ordinary A/C units start.

7-2-3. Compressor Temperature Control

To protect the compressor coil from overheating, the operating frequency is controlled based on the compressor discharge temperature.

Compressor discharge temperature

F)

Trip

(230)

5Hz every 30 sec. reduction

(223)

2Hz every 30 sec. reduction

(212)

Increase

prohibit range

No control

(Hz reduction)

(194)

*Within the increase-prohibit range, the range changes to the Hz reduction range (2 Hz every 30 seconds) if the compressor temperature rises by 4 °F.