install the indoor unit more than 3.3' (1 m) away from any antenna or power lines or connecting wires used for tele- vision, radio, telephone, security system, or intercom.

Electrical noise from any of these sources may affect operation.

install in a sturdy manner to avoid increased operating noise.

Table 3

 

Max.

Max. Allowable Total

 

Limit of

Limit of Elevation

Required Amount

 

Allowable

Tubing Length

Total Tubing Length

Difference

of Additional

Model

Tubing Length

at Shipment

(L1+L2+L3) or

(H1, H2, H3, H4)

Refrigerant

 

Per Unit

(L1+L2+L3) or

(L1+L2+L3+L4)

(ft.)

(oz./ft.)*

 

(ft.)

(L1+L2+L3+L4)

 

(ft.)

 

 

 

 

 

(ft.)

 

 

 

 

 

 

 

 

 

 

 

 

CU-3KS19NBU

82

150

(L1+L2+L3)

150

(L1+L2+L3)

50

 

 

 

 

 

 

 

 

CU-4KS24NBU

82

150

(L1+L2+L3+L4)

200

(L1+L2+L3+L4)

50

0.22

 

 

 

 

 

 

 

 

CU-4KS31NBU

100

150

(L1+L2+L3+L4)

230

(L1+L2+L3+L4)

50

0.22

 

 

 

 

 

 

 

 

*If total tubing length becomes 150 to 200 ft. (Max.) or 150 to 230 ft. (Max.), charge additional refrigerant (R410A) by 0.22 oz./ft.

No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.

6

Page 92
Image 92
Panasonic CU-4KS31NBU service manual H1, H2, H3, H4