Panasonic CU-4KS31NBU service manual Max. Allowable Total, Limit of Elevation, Required Amount

Models: CU-4KS31NBU

1 114
Download 114 pages 23.14 Kb
Page 92
Image 92

install the indoor unit more than 3.3' (1 m) away from any antenna or power lines or connecting wires used for tele- vision, radio, telephone, security system, or intercom.

Electrical noise from any of these sources may affect operation.

install in a sturdy manner to avoid increased operating noise.

Table 3

 

Max.

Max. Allowable Total

 

Limit of

Limit of Elevation

Required Amount

 

Allowable

Tubing Length

Total Tubing Length

Difference

of Additional

Model

Tubing Length

at Shipment

(L1+L2+L3) or

(H1, H2, H3, H4)

Refrigerant

 

Per Unit

(L1+L2+L3) or

(L1+L2+L3+L4)

(ft.)

(oz./ft.)*

 

(ft.)

(L1+L2+L3+L4)

 

(ft.)

 

 

 

 

 

(ft.)

 

 

 

 

 

 

 

 

 

 

 

 

CU-3KS19NBU

82

150

(L1+L2+L3)

150

(L1+L2+L3)

50

 

 

 

 

 

 

 

 

CU-4KS24NBU

82

150

(L1+L2+L3+L4)

200

(L1+L2+L3+L4)

50

0.22

 

 

 

 

 

 

 

 

CU-4KS31NBU

100

150

(L1+L2+L3+L4)

230

(L1+L2+L3+L4)

50

0.22

 

 

 

 

 

 

 

 

*If total tubing length becomes 150 to 200 ft. (Max.) or 150 to 230 ft. (Max.), charge additional refrigerant (R410A) by 0.22 oz./ft.

No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.

6

Page 92
Image 92
Panasonic CU-4KS31NBU service manual Max. Allowable Total, Limit of Elevation, Required Amount, H1, H2, H3, H4