Panasonic CU-4KS31NBU service manual CS-MKS9NB4U×

Models: CU-4KS31NBU

1 114
Download 114 pages 23.14 Kb
Page 55
Image 55
: CS-MKS9NB4U × 4

Outdoor Unit

: CU-4KS31NBU

 

 

 

 

 

 

 

 

 

Indoor Unit

: CS-MKS9NB4U × 4

 

 

 

 

 

 

 

 

 

Power Supply : 230V Single Phase 60Hz

 

 

 

 

 

 

 

 

 

< Cooling Capacity >

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RATING CAPACITY:

28,600 BTU/h

 

AIR FLOW RATE:

883 CFM

 

INDOOR

 

 

 

 

 

OUTDOOR

 

 

 

 

 

ENT. TEMP. o F (o C)

 

 

 

AMBIENT TEMP. o F (o C)

 

 

 

WB

 

DB

 

 

65

75

85

 

95

105

115

 

 

 

 

 

 

(18.3)

(23.9)

(29.4)

 

(35.0)

(40.6)

(46.1)

 

 

 

 

 

TC

28,830

27,880

26,840

 

26,270

21,300

15,500

 

 

72

(22.2)

 

SHC

22,560

22,210

21,700

 

21,360

19,130

15,500

 

59

76

(24.4)

 

SHC

25,810

25,470

24,960

 

24,610

21,300

15,500

 

(15.0)

80

(26.7)

 

SHC

28,830

27,880

26,840

 

26,270

21,300

15,500

 

 

84

(28.9)

 

SHC

28,830

27,880

26,840

 

26,270

21,300

15,500

 

 

88

(31.1)

 

SHC

28,830

27,880

26,840

 

26,270

21,300

15,500

 

 

 

 

 

TC

29,960

29,000

27,940

 

27,440

21,790

15,830

 

 

72

(22.2)

 

SHC

18,780

18,270

17,930

 

17,580

15,360

12,960

 

63

76

(24.4)

 

SHC

22,040

21,700

21,180

 

21,010

18,610

15,830

 

(17.2)

80

(26.7)

 

SHC

25,470

25,130

24,610

 

24,440

21,790

15,830

 

 

84

(28.9)

 

SHC

28,730

28,390

27,870

 

27,440

21,790

15,830

 

 

88

(31.1)

 

SHC

29,960

29,000

27,940

 

27,440

21,790

15,830

 

 

 

 

 

TC

31,060

30,090

29,010

 

#

28,600

22,220

16,110

 

 

72

(22.2)

 

SHC

14,840

14,500

13,980

 

13,810

11,410

9,180

 

67

76

(24.4)

 

SHC

18,100

17,760

17,410

 

17,240

14,670

12,440

 

(19.4)

80

(26.7)

 

SHC

21,530

21,180

20,840

 

20,670

18,100

15,870

 

 

84

(28.9)

 

SHC

24,780

24,440

24,100

 

23,930

21,360

16,110

 

 

88

(31.1)

 

SHC

28,210

27,700

27,360

 

27,180

22,220

16,110

 

 

 

 

 

TC

32,080

31,110

30,020

 

29,730

22,560

16,340

 

 

72

(22.2)

 

SHC

10,730

10,380

10,040

 

9,870

7,470

5,410

 

71

76

(24.4)

 

SHC

13,980

13,640

13,300

 

13,130

10,730

8,670

 

(21.7)

80

(26.7)

 

SHC

17,410

17,070

16,730

 

16,560

14,160

12,100

 

 

84

(28.9)

 

SHC

20,670

20,330

19,980

 

19,810

17,410

15,360

 

 

88

(31.1)

 

SHC

23,930

23,580

23,240

 

23,240

20,670

16,340

 

 

 

 

 

TC

32,920

31,940

30,850

 

30,690

22,770

16,470

 

75

76

(24.4)

 

SHC

10,040

9,700

9,360

 

9,360

6,780

4,900

 

(23.9)

80

(26.7)

 

SHC

13,470

13,130

12,780

 

12,780

10,210

8,330

 

 

84

(28.9)

 

SHC

16,730

16,380

16,040

 

16,040

13,470

11,760

 

 

88

(31.1)

 

SHC

19,980

19,640

19,300

 

19,300

16,730

15,010

TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)

NOTE

1.Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB

:Outdoor Ambient Temp. 95 °F (35 °C) DB

2.Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.

3.Above data represents the value when the operation frequency of a compressor is fixed.

55