MACH® Series | Parts and Technical Support |
|
|
6.1WIRING DIAGRAMS
6.1.1 Terminal Block Assignments – High Voltage Circuit (TB2)
Terminal Number | Label | Description | |
|
|
| |
|
|
| |
1 | 115 VAC LINE | Boiler Supply Power, 115 VAC, 60 HZ, 1 ph, 8 amp | |
|
|
| |
2 | 115 VAC NEUTRAL |
| |
|
|
| |
3 | 115 VAC NEUTRAL | Aux. Switched Output | |
|
|
| |
4 | 115 VAC NEUTRAL | Boiler Circ. Pump | |
|
|
| |
5 | 115 VAC NEUTRAL | DHW Circ. Pump | |
|
|
| |
6 | GROUND | Boiler Supply Ground | |
|
|
| |
7 | GROUND | Aux .Ground | |
|
|
| |
8 | GROUND |
| |
|
|
| |
9 | 115 VAC SW. OUTPUT | Aux. Switched Output, Pilot duty only, 1 amp max. | |
|
|
| |
10 | 115 VAC CIRC. PMP | Boiler Circ. Pump, Pilot duty only, 1 amp max. | |
| CONTACTOR |
| |
|
|
| |
|
|
| |
11 | 115 VAC DHW PMP | DHW Circ. Pump, Pilot Duty only, 1 amp max. | |
| CONTACTOR |
| |
|
|
| |
12 | MASTER ALARM RELAY | Dry Contacts, 24 VAC max, 1 amp max. | |
|
|
| |
13 | MASTER ALARM RELAY |
| |
|
|
| |
14 | THREE WAY VALVE RELAY | DHW Dry Contacts, 24 VAC max, 1 amp max. | |
|
|
| |
15 | THREE WAY VALVE RELAY |
| |
|
|
| |
16 | DAMPER RELAY | Combustion Air Damper, Dry Contacts, 24 VAC max, 1 amp | |
|
| max. | |
17 | DAMPER RELAY | ||
| |||
|
|
| |
|
|
|
Page 37