MACH® Series | Installation |
|
|
This port is located on the upstream side of the valve body for measuring supply pressure. (See figure below.)
Boiler Test Mode:
The test mode should be used when checking and setting the gas safety shut off / control valves on the MACH Series boilers. In this mode an automatic heat request is simulated as follows:
Test Mode High:
Simultaneously pressing the “Mode” button and the “+” button for 3 seconds activates the “Test Mode High” function to drive the boiler output to maximum. The display will blink and indicate “H” in the first digit of the display to indicate the boiler is being driven to the maximum output rating. This test mode will automatically terminate after 15 minutes or can be terminated from the control/display panel by simultaneously pressing the “+” and
Test Port
Gas Pressure Test Port
Test Mode Low:
The supply pressure during main burner operation must be greater than the minimum indicated on the rating plate (3.5". W.C. for natural gas, 7" W.C. for propane).
3.12.3 Air Flow Adjustments
The air flow is
Combustion measurement instrumentation must be used to adjust the boiler for local conditions (See instructions below). Adjust the carbon dioxide (CO2) or oxygen (O2) reading to achieve conditions as listed in the following Table
3.12.4 Gas Valve Setup and Adjustment
Note: Verify gas pressure at inlet to boiler is in accordance with Table
Page 25
Simultaneously pressing the “Mode” button and the
MACH C300 & C450
Required Tools:
2 mm hex wrench Slotted screwdriver Combustion analyzer
The MACH C300 and C450 boilers are equipped with two combined gas/air control and gas safety shut off control valves. The valves function in parallel with the variable speed combustion blower to supply the correct gas air ratio for optimum performance and efficiency. The combustion blower speed is controlled automatically and determines the amount of negative pressure felt at the gas safety shut off / control valves. The gas valve servo regulators adjust gas flow for each valve to maintain zero pressure at the outlet nozzle of the associated valves.