Parameter Settings for MCBA Controls
Parameter Settings for MCBA Controls
No. | Description | Lower Limit | Upper Limit |
|
|
|
|
|
|
|
|
|
| Installed | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| MCBA |
|
|
|
|
|
| MACH | MACH | MACH | MACH | MACH | Parameter | |||||
|
|
|
|
|
| Settings | ||||||||||
|
|
|
|
|
| 300 PK | 450 PK | 750 PK | 900 PK | 1050 PK |
| |||||
|
|
|
|
|
| Factory | Factory | Factory | Factory | Factory |
| |||||
|
|
|
|
|
| Setting | Setting | Setting | Setting | Setting |
| |||||
|
|
|
|
|
| for MCBA | for MCBA | for MCBA | for MCBA | for MCBA |
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| End User Settings |
|
|
|
| NG | LPG | NG | LPG | NG | LPG | NG | LPG | NG | LPG |
|
1 | Setvalue for DHW | Water Storage Tank: 68 F | Water Storage Tank: 158 F | 140 | 140 | 140 | 140 | 140 | 140 | 140 | 140 | 140 | 140 |
| ||
2 | DHW system | 0 | = off |
|
| 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
|
|
| 1 | = on |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2 | = off+ pump continuous |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 3 | = on+ pump continuous |
|
|
|
|
|
|
|
|
|
|
|
|
|
3 | CH system | 0 | = off |
|
| 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
|
|
| 1 | = on |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2 | = off+ pump continuous |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 3 | = on+ pump continuous |
|
|
|
|
|
|
|
|
|
|
|
|
|
4 | Setpoint or Maximum Setpoint (OAR) | 68 F | 182 | 180 | 180 | 180 | 180 | 180 | 180 | 180 | 180 | 180 | 180 |
| ||
| Service Settings |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5 | Minimum Setpoint, Outdoor Air Reset (OAR) | 60 F | 140 F | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 |
| ||
6 | Minimum outdoor temp (OAR) | 50 | F | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 |
| ||
7 | Maximum outdoor temp (OAR) | 59 F | 77 F | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 |
| ||
8 | Frost protection, at OA Temp | 50 | F | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 |
| ||
9 | Correction, Outdoor Air Sensor | 9 F | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| |||
10 | CH shutdown setpoint temp (OAR) | 32 = off |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| 34 F | 140 F | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 | 32 |
| ||
11 | Booster time | 0 | = no booster |
|
| 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
|
|
| 1 minute | 30 minutes |
|
|
|
|
|
|
|
|
|
|
| ||
12 | Outdoor Air Offset | 0 | F | 144 F | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| |
13 | Maximum fanspeed CH (hundreds) | 10 | 70 |
| 60 | 57 | 56 | 54 | 49 | 48 | 56 | 54 | 60 | 58 |
| |
14 | Maximum fanspeed CH (units) | 00 | 99 |
| 00 | 00 | 00 | 00 | 00 | 50 | 00 | 00 | 00 | 00 |
| |
15 | Maximum fanspeed DHW (hundreds) | 10 | 70 |
| 60 | 57 | 56 | 54 | 49 | 48 | 56 | 54 | 60 | 58 |
| |
16 | Maximum fanspeed DHW (units) | 00 | 99 |
| 00 | 00 | 00 | 00 | 00 | 50 | 00 | 00 | 00 | 00 |
| |
17 | Minimum fanspeed (hundreds) | 5 |
| 70 |
| 16 | 20 | 12 | 20 | 11 | 13 | 13 | 13 | 13 | 13 |
|
18 | Minimum fanspeed (units) | 00 | 99 |
| 00 | 00 | 00 | 00 | 50 | 00 | 00 | 00 | 00 | 00 |
| |
19 | Ignition fanspeed (hundreds) | 5 |
| 70 |
| 35 | 35 | 25 | 25 | 22 | 22 | 22 | 22 | 22 | 22 |
|
20 | Postpumptime CH | 0 | = 10 Seconds |
|
| 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
|
|
| 1 | Minute | 99 | Minutes |
|
|
|
|
|
|
|
|
|
|
|
21 | Postpumptime DHW | 0 | Seconds | 30 x 10.2 seconds | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 |
| |
22 | CH modulation hysteresis On | 0 | F | 36 | F | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
|
23 | CH modulation hysteresis Off | 0 | F | 18 | F | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
|
24 | DHW modulation hysteresis On | 54 | F | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
| ||
25 | DHW modulation hysteresis Off | 54 | F | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
| ||
26 | DHW detection hysteresis On | 54 | F | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
|