Patterson-Kelley MACH-05 Internal Setpoint, Domestic Priority, Parameter, Value, Allowable, Range

Models: MACH-05

1 59
Download 59 pages 32.78 Kb
Page 26
Image 26
Internal Setpoint:

MACH® Series Gas-Fired Boiler

Internal Setpoint:

The internal setpoint is set with parameter 4. The boiler temperature control modulates the boiler to maintain this internal setpoint. The upper and lower temperature differentials are used to instruct the boiler at what temperature to turn on and at what temperature to turn off.

Item

Parameter

Value

Allowable

 

 

 

Range

 

 

 

 

Setpoint

4

160

68-185

 

 

 

 

Low Temp. Differential

22

10

0-36

 

 

 

 

High Temp. Differential

23

9

0-36

 

 

 

 

Low Temp. Setpoint

5

68

59-140

 

 

 

 

The boiler will modulate to try to maintain 160° F. If the temperature increases above 169° F which is the setpoint 160° F + High Temp Differential 9°F the boiler will shut off. Once it shuts off it will not restart until the temperature drops below 150° F which is the setpoint – Low Temp Differential. The Low Temp Set Point will not permit the operator to adjust the setpoint below 68° F. (See graph below.)

 

 

Internal Setpoint

 

175

 

 

 

 

170

 

 

Boiler Turns Off

 

 

 

 

 

165

Boiler Temperature

 

 

160

 

Boiler Set Point

 

155

 

 

 

 

 

 

150

Boiler Turns On

 

 

 

 

 

 

145

 

 

 

 

0

10

20

30

40

 

 

Time

 

 

Domestic Priority:

If an indirect domestic hot water (DHW) tank is connected, the DHW function of the boiler will activate when the DHW temperature controller (supplied by others) closes (Terminal 5 to 8 TB 1, refer to Section 6.1.1), indicating a call for heat from the DHW system. The parameters should be set as follows:

 

 

Installation

 

 

 

 

 

Item

Parameter

 

Value

 

 

 

 

 

 

DHW Setpoint

1

 

140

 

 

 

 

 

 

DHW Setpoint Addition

33

 

30

 

 

 

 

 

 

DHW Status

2

 

1

 

 

 

 

 

 

DHW High Temp. Differential

25

 

6

 

 

 

 

 

 

DHW Low Temp. Differential

24

 

6

 

 

 

 

 

 

DHW Options

35

 

13

 

 

 

 

 

 

In the above example, the boiler temperature will be set to the DHW Setpoint + the DHW Setpoint Addition (140ºF + 30ºF = 170ºF) when the DHW temperature controller indicates a call for heat from the DHW system. When the DHW system calls for heat, the Central heat pump output (Terminal 10 TB2) de-energizes and the DHW pump output (Terminal 11 TB2) energizes providing 120 VAC power is provided to energize a relay coil for the DHW pump. The DHW status should be set to 1 (DHW system ON).

Page 22

Page 26
Image 26
Patterson-Kelley MACH-05 manual Internal Setpoint, Domestic Priority, Parameter, Value, Allowable, Range