MACH® Series | Installation |
|
|
First Digit | Boiler Status |
|
|
| delay. No system call for heat. |
|
|
| Burner off - Domestic Hot Water pump |
8 | running on delay. No system call for heat. |
|
|
| Burner off – auto reset lockout. A code is |
| displayed indicating the reason for the |
9 and b | lockout. (See Troubleshooting Section |
flashing | 5.5.) |
|
|
A | Adjusting the 3 way valve if used |
|
|
H | Burner on in manual high fire |
|
|
L | Burner on in manual low fire |
Parameter Mode:
The parameter mode is used to change the settings of the boiler. The parameter mode is accessed by pressing the MODE key several times until the display shows PArA.
The parameters are selected with the STEP key, and changed with the plus “+” and minus
Parameters 1 through 4 are accessible directly at the parameter level.
Parameters higher than 4 are only accessible by authorized service personnel trained on the
|
|
| Upper |
Parameter | Description | Lower Limit | Limit |
|
|
|
|
| DHW setpoint |
|
|
1 | if used | 68° | 158° |
|
|
|
|
2 | DHW system | 0=OFF |
|
| ON/OFF | 1=ON |
|
|
|
| |
|
| 2=OFF +pump |
|
|
| continuous |
|
|
| 3=ON + pump |
|
|
| continuous |
|
|
|
|
|
3 | Comfort heat | 0=OFF |
|
| system | 1=ON |
|
| ON/OFF |
| |
| 2=OFF +pump |
| |
|
|
| |
|
| continuous |
|
|
| 3=ON + pump |
|
|
| continuous |
|
| Setpoint or |
|
|
| max boiler |
|
|
| temp outdoor |
|
|
4 | air mode | 68° | 182° |
|
|
|
|
Page 21
Information Mode:
The information mode is used to display the values of the various sensors such as inlet water temp, outlet water temp etc. The information mode is accessed by pressing the MODE key several times until InFo is displayed. The desired sensor is selected with the STEP key. The following table indicates the displayed value:
Step | Value |
1Outlet water temp
2Inlet water temp
3Domestic Hot Water temp *
4Outdoor air temp *
5Flue gas temp
6Boiler outlet setpoint
7Rate of change outlet temp °F/second
8Rate of change inlet temp °F/second Rate of change Domestic Hot Water
9°F/second
Second Comfort Heat system
Atemperature
*If the sensors for these functions are not installed, the display will indicate
3.12.1.2 Operating Configurations
The boiler has several different operating configurations. These are:
•Internal Setpoint
•Domestic Priority
•Outdoor Air Reset
•Analog Input Setpoint
•Analog Input Direct Drive
CAUTION!
Do not modify any parameters other than those specifically mentioned.