Pelco 2 C1306M-B (10/06) Dip Switch Settings, Protocol Settings, RECEIVER ADDRESS SETTINGS SW1

Models: 2 C1306M-B (10/06) C1306M-B (10/06)

1 24
Download 24 pages 1.68 Kb
Page 7
Image 7
DIP SWITCH SETTINGS

DIP SWITCH SETTINGS

Configure the receiver address, termination, and baud setting for the system. The DIP switches to configure these settings are located on the top of the power module.

NOTE: No DIP switch settings are required for Coaxitron control.

Figure 3 shows the default settings for the DIP switches. Refer to the following to configure the ExSite system settings.

SW1-1 is set to the ON position.

All other switches are set to the OFF position.

1

2 3

4

5

6

7 8

 

 

SW1

 

on

 

 

 

 

 

1 PROTOCOL SETTINGS SW2RECEIVER ADDRESS SETTINGS (SW1)

TERMINATION SETTING (SW2)1 on

2 3

4

5

6

7 8

 

SW3

 

 

ON

Figure 3. Default DIP Switch Settings

PROTOCOL SETTINGS

The ExSite system automatically detects the type of protocol. No switch settings are required to set Coaxitron or RS-422 P and D protocols.

RECEIVER ADDRESS SETTINGS (SW1)

The default address is 2 for P protocol. Refer to Table A for address settings that use P protocol. Maximum number of receivers is 32.

The default address is 1 for D protocol. Refer to Table B for address settings that use D protocol. Maximum number of receivers is 254.

TERMINATION SETTING (SW2)

When connecting more than one ExSite system to a single controller, terminate the unit farthest from the controller. Termination is required only for the last unit in the series. The unit is shipped from the factory in the unterminated OFF position. To terminate the unit, set the SW2 switch to the ON position.

BAUD SETTINGS (SW3)

Pelco’s D-type controllers are set for 2400 baud. The default setting for the unit is 2400 baud. If you are using a Pelco D-type controller, do not reset the SW3 switches.

P-type controllers can operate at 2400, 4800, and 9600 baud. Set the SW3 switches (6, 7, and 8), located on the top of the power module, to the same baud as the P-type controller.

Switch Settings for SW3

Switch Number

SW3-6

SW3-7

SW3-8

 

 

 

 

2400 Baud

Off

Off

Off

 

 

 

 

4800 Baud

On

Off

Off

 

 

 

 

9600 Baud

Off

On

Off

 

 

 

 

C1306M-B (10/06)

7

Page 7
Image 7