Polycom RMX 4000 Hardware Guide

The airflow of the RMX 4000 is from right to left. Be sure that the areas on the left and right side of the system are clear for proper

ventilation.

When the unit is installed on a rack, the rack must be properly grounded to the central office ground. The rack must be grounded with two-hole compression- type connectors using copper conductors (tinned or untinned). Wire, bus bar or braided strap connectors are acceptable.

Reverse Mounting the RMX 4000 in a Rack

It is possible to reverse mount the RMX 4000 in a rack using 19” or 23” brackets.

To reverse mount the RMX 4000 on a 19” rack:

1Remove the handles and brackets from the front of the RMX.

2Attach the brackets to the rear of the RMX.