Powerware 2500 manual Chapter Configuration

Models: 2500

1 78
Download 78 pages 30.38 Kb
Page 47
Image 47

Chapter 5

Configuration

When the UPS is in Configuration mode, the bar graph indicators represent the configuration options. Use the control buttons

(On button and button) to modify the UPS configuration. Figure 33 shows the LEDs and Table 2 explains the corresponding options.

NOTE The UPS can be configured while in Battery mode. If the UPS transfers to battery power while in Configuration mode, the UPS remains in Configuration mode and indicates Battery mode on the front panel after exiting Configuration mode.

To reconfigure the UPS default settings:

1. Press and hold the On button and the

button simultaneously

for one beep. The UPS transfers to Configuration mode.

The LEDs flash briefly and then display the enabled options.

2. Press the On button to scroll through the options. Each time you press the button, the UPS beeps. The LED for the selected option indicates the current setting; flashing represents disabled options (see Figure 33 and Table 2).

Scrolling past the last LED returns to the first configuration option.

If you press the On button and nothing happens, the UPS is still in Operation mode. Repeat Step 1 to enter Configuration mode, and then perform Step 2.

3.Press the button for approximately one second to select the Voltage option or to toggle the Site Wiring Fault Alarm or AC Input Failure Alarm on or off.

NOTE The UPS exits Configuration mode automatically after two minutes of inactivity.

4. Press and hold the On button and the

button simultaneously to

exit Configuration mode at any time.

 

EATON Powerware® 9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D

41

www.powerware.com

 

Page 47
Image 47
Powerware 2500 manual Chapter Configuration