Raypak 406A Heat Exchanger Pressure Drop Tables, Polymer Header Standard Models, Flow, 406/407

Models: 266A 267A 207A 336A 337A 407A 206A 406A

1 55
Download 55 pages 6.49 Kb
Page 24
Image 24

HEAT EXCHANGER PRESSURE DROP TABLES

POLYMER HEADER (STANDARD MODELS)

FLOW

PRESSURE DROP (FT OF HEAD)

GPM

206/207

266/267

336/337

406/407

 

 

 

 

 

20

1.5

2.8

4.1

4.1

 

 

 

 

 

30

1.7

4.6

5.8

5.8

 

 

 

 

 

40

2.1

5.2

6.5

6.5

 

 

 

 

 

50

2.4

5.6

7.2

7.2

 

 

 

 

 

60

2.8

6.1

7.7

7.7

 

 

 

 

 

70

3.7

6.5

8.2

8.2

 

 

 

 

 

80

4.6

7.3

8.7

8.7

 

 

 

 

 

90

5.7

8.8

10.2

10.2

 

 

 

 

 

100

6.8

10.0

13.0

13.0

 

 

 

 

 

CAST IRON HEADER (ASME MODELS)

FLOW

PRESSURE DROP (FT OF HEAD)

GPM

206/207

266/267

336/337

406/407

 

 

 

 

 

20

1.8

3.9

3.9

3.9

 

 

 

 

 

30

2.2

8.0

8.0

8.0

 

 

 

 

 

40

2.5

9.0

9.0

9.0

 

 

 

 

 

50

2.7

9.8

9.8

9.8

 

 

 

 

 

60

3.3

10.5

10.5

10.5

 

 

 

 

 

70

4.3

11.0

11.0

11.0

 

 

 

 

 

80

5.5

11.5

11.5

11.5

 

 

 

 

 

90

6.8

14.0

14.0

14.0

 

 

 

 

 

100

8.2

17.0

17.0

17.0

 

 

 

 

 