Raypak 207A, 406A, 206A, 407A, 337A, 336A Electrical - Electronic Ignition Iid Warning High Voltage

Models: 266A 267A 207A 336A 337A 407A 206A 406A

1 55
Download 55 pages 6.49 Kb
Page 45
Image 45

ELECTRICAL - ELECTRONIC IGNITION IID

WARNING HIGH VOLTAGE

For qualified technicians ONLY

NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater.

START

TURN GAS SUPPLY OFF.

TURN THERMOSTAT

(CONTROLLER) TO CALL

FOR HEAT

POWER TO PC BOARD?

(24 V NOMINAL)

YES

SPARK ACROSS

IGNITER/SENSOR GAP?

YES

TURN GAS SUPPLY ON PILOT BURNER LIGHTS?

YES

NO

NO

NO

NOTE: Before troubleshooting, familiarize yourself with the start-up and check-out procedure.

Check line voltage power, low voltage transformer, limit controller, thermostat (controller) and wiring.

Pull ignition lead and check spark at PC board.

Spark Okay?

YES NO

Replace the PC board.

Check ignition cable, ground wiring, ceramic insulator and gap, and correct.

Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield cable and boot from excessive temperatures.

Check that all manual gas valves are open, supply tubing and pressures are good, and pilot burner orifice is not blocked.

Check electrical connections between PC board and pilot operator on gas control.

Check for 24 VAC across PV-MV/PV terminals on PC board. If voltage is okay, replace gas control; if not, replace PC board.

NOTE: If PC board goes into lockout, reset system. Lockout is used on L.P.G. models.

MAIN BURNER LIGHTS? NO YES

Check for 24 VAC across MV-MV/PV terminals. If no voltage, replace module.

Check electrical connections between PC board and gas control. If okay, replace gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.

SYSTEM RUNS UNTIL CALL FOR HEAT ENDS?

YES

CALL FOR HEAT ENDS SYSTEM SHUTS OFF?

YES

TROUBLESHOOTING

ENDS

NO

NO

NOTE: IF PC board goes into lockout, reset system.

• Check continuity of ignition cable and ground wire.

NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at the time of checkout.

Check that pilot flame covers flame rod and is steady and blue.

If checks are okay, replace PC board.

Check for proper thermostat (controller) operation.

Remove MV lead at module; if valve closes, recheck temperature controller and wiring; if not, replace gas valve.

45

Page 45
Image 45
Raypak 207A, 406A, 206A, 407A, 337A Electrical - Electronic Ignition Iid Warning High Voltage, For qualified technicians ONLY