Regency P33R-LP2, P33R-NG2 installation manual Horizontal Installations

Models: P33R-NG2 P33R-LP2

1 40
Download 40 pages 27.95 Kb
Page 18
Image 18
HORIZONTAL INSTALLATIONS

INSTALLATION

HORIZONTAL INSTALLATIONS

Install the vent system according to the manu- facturer's instructions included with the com- ponents.

1)Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is at- tached. If this is the case, you may want to adjust the location of the unit. Rough in the gas preferably on the right side of the unit and the electrical (junction block is on the left side) on the left.

2)Direct Vent pipe and fittings are designed with special twist-lock connections to con- nect the venting system to the appliance flue outlet. A twist-lock appliance adaptor is an available option that must be used in conjunction with the Simpson Dura-Vent Direct Vent GS system.

3)Put a bead of silicone inside the outer section of the adapter and a bead of Stove Mate on the inner collar. Slip the adapter over the existing inner and outer flue collar and fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier). Level the fireplace and fasten it to the framing using nails or screws through the nailing strips.

4)Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.

Note:

a) Twist-lock procedure: Four indentations,

located on the female ends of pipes and

fittings, are designed to slide straight

onto the male ends of adjacent pipes

and fittings, by orienting the four pipe

indentations so they match and slide in

to the four entry slots on the male ends,

Dia. 1. Push the pipe sections complete-

ly together, then twist-lock one section

clockwise approximately one-quarter

turn, until the two sections are fully

locked. The female locking lugs will not

b)Horizontal runs of vent must be sup- ported every three feet. Wall straps are available for this purpose.

5)Mark the wall for a 10" x 10" square hole. The center of the square hole should line up with the centerline of the horizontal pipe. Cut and frame the 10 inch square hole in the exterior wall where the vent will be termi- nated. If the wall being penetrated is con- structed of non-combustible material, i.e. masonry block or concrete, a 7"(178mm) diameter (7-1/2"(191mm) dia. for flex) hole is acceptable. See Horizontal Termination diagram on page 14.

Note: With Dura-Vent, the minimum height is achieved by installing a 90o elbow directly to the flue adapt- er.

Note:

a)The horizontal run of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fire.

b)The location of the horizontal vent ter- mination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. For External Vent Terminal Locations, see diagram on page 9.

c)Snorkel Terminations:

For installations requiring a vertical rise on the exterior of the building, 14-inch and 36-inch tall Snorkel Terminations and the Riser Vent as shown in Dia. 2 & 2a are available. Follow the same installation procedures as used for standard Horizontal Termination. NEV- ER install the snorkel upside down.

Diagram 2a

Below Grade Snorkel Installation If the Snorkel Termination must be in- stalled below grade, i.e. basement ap- plication, proper drainage must be pro- vided to prevent water from entering the Snorkel Termination. Refer to Dura- Vent Installation instructions for de- tails. Do not attempt to enclose the Snorkel within the wall, or any other type of enclosure.

6)The arrow on the vent cap should be pointing up. Insure that the 1-1/2" clear- ances to combustible materials are main- tained (Dia. 3). Install the termination cap. AstroCapTM or Dura-Vent Horizontal Ter- mination Cap may be used.

be visible from the outside, on the Black

Pipe or fittings. They may be located by

examining the inside of the female ends.

Diagram 1

Note: Apply sealant "Mill-Pac" to inner pipe and high temperature sili- cone sealant to outer pipe on eve- ry twist-lock joint.

Diagram 2

*As specified in CGA B149 Installation Code. Local codes or regulations may require differ- ent clearances.

Diagram 3

The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.

Note: If installing termination on a siding covered wall, a vinyl siding stand- off or furring strips must be used to ensure that the termination is not recessed into the siding.

7)Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Thimble (Part # 620-926) over the vent pipe.

8)Slide the appliance and vent assembly to- wards the wall carefully inserting the vent

18

Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace

Page 18
Image 18
Regency P33R-LP2, P33R-NG2 installation manual Horizontal Installations