Regency P42-LP3 Rigid Pipe Venting Arrangements Vertical Terminations, Propane & Natural Gas

Models: P42-LP3 P42-NG3

1 44
Download 44 pages 17.93 Kb
Page 15
Image 15

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS

(Propane & Natural Gas)

The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations with rigid pipe vent systems for Propane and Natural Gas.

Maximum two 45o elbows allowed.

Vent restrictor #6 must be used in shaded area in diagram below.

Vent must be supported at offsets

The P42 is approved for a 37 ft. (11.3m) straight ver- tical, including a 20" (0.5m) horizontal offset using two 90o elbow (two 45o elbows equal one 90o el- bow) with rigid pipe vent systems for Propane and Natural Gas, as per the diagram to the right.

Vent restrictor #6 is required for ter- minations in shad- ed area.

Vent must be sup- ported at offsets

Diagram 1

Note: Must use optional rigid pipe adap- tor when using rigid pipe vent systems (Part # 510-994).

Note: Regency Direct Vent System (Flex) is only approved for horizontal ter- minations.

Diagram 2

Regency P42-3 Zero Clearance Direct Vent Gas Fireplace

15