Regency U39-NG1, U39-LP1 Installation, Dura-Vent Termination Kit, Dura-Ventventing Components

Models: U39-LP1 U39-NG1

1 44
Download 44 pages 36.34 Kb
Page 17
Image 17
DURA-VENT

INSTALLATION

DURA-VENT

TERMINATION KIT

Planning Your Dura-Vent

Installation

There are two basic types of Dura-Vent Direct VentSystem installations:horizontaltermination and vertical termination. Confi rm the maximum horizontal run and maximum vertical rise from the diagrams in the "Rigid Pipe Venting Arrangements" section.

When planning your installation, it will be necessary to select the proper length of vent pipe for your particular requirements. For horizontal installations, determine the minimum clearance from the rear of the unit to the wall. It is also important to note the wall thickness. (The wall thimble is suitable for 2 x 4 or 2 x 6 wall construction.) Select the amount of vertical rise desired for "vertical-to-horizontal" type installations.

Warning: Always maintain required clearances (air spaces) to nearby combustibles to prevent a fire hazard. Do not fill air spaces with insulation.

The minimum clearance requirements between the outer wall of the vent pipe and nearby combustible surfaces is 1-1/4 inch. Be sure to check the vent termination clearance requirements from decks, windows, soffi ts, gas regulators, air supply inlets and public walkways as specifi ed in the "Exterior Vent Terminal Locations" section and in your local building codes.

DURA-VENT VENTING

COMPONENTS

You will require the following components with your new Regency® Direct Vent Freestanding Gas Stove. Please review your product to make sure you have everything you need. In the event that you are missing any part, contact your dealer.

Note: These are the minimum pieces required.Otherpartsmayberequired for your particular installation. See the "Dura-vent Horizontal Kit" section for a list of vent parts.

If installing termination on a siding covered wall, a vinyl siding standoff or furring strips can be used in order to ensure that the termination is not recessed into siding.

The vinyl siding standoff is required for walls with vinyl siding.

Minimum components for a Dura-Vent Horizontal Installation:

A)Dura-Vent Horizontal Termination Kit

B)Wall Thimble (required for combus- tible walls)

Minimum components for a Dura-Vent Vertical Termination:

C)Dura-Vent Vertical Termination Kit See the "Rigid Pipe Venting Arrangments" section for pipe lengths.

The Simpson Dura-Vent Direct Vent System offers a complete line of component parts for installation of both horizontal and vertical installation. Many items are offered in decorative black, as well as galvanized finish. The galvanized pipe and fittings are used for concealed locations such as attics or where corrosion is a factor, such as above the roof line. Decorative brass trim kits are available for both wall thimbles and ceiling support boxes.

To determine the length of vent pipe required for vertical installations, measure the distance from the unit fl ue outlet to the ceiling, the ceiling thickness, the vertical rise in an attic or second storey, and allow for sufficient vertical height above the roof line.

For multi-storey applications, fi re stops are required at each fl oor level. If an offset is needed, additional pipe, elbows and supports will be required.

Dura-Vent Basic

Horizontal Kit # 970

190o Elbow

1Wall Thimble Cover

1Horiz. Sq. Term. Cap

Alternate Horizontal

Termination Caps

Regency® U39 ULTIMATE Direct Vent Freestanding Gas Stove

17

Page 17