Regency® U39 ULTIMATE Direct Vent Freestanding Gas Stove
9
|
|
|
| EXTERIOR VENT TERMINAL |
A= | Clearance above grade, veranda, porch, deck, or balcony *(min. |
| with | LOCATIONS |
|
| |||
| 12"/30cm) | H= | Not to be installed above a meter/regulator assembly within (3'/90cm) |
|
B= | Clearance to window or door that may be opened *(12"/30cm) |
| horizontally from the centerline of the regulator. |
|
C= | Clearance to permanently closed window *(min. 12"/30cm) | J= | Clearance to service regulator vent outlet *(min. 36"/90cm) |
|
D= | Vertical clearance to ventilated soffit located above the terminal within a | K= | Clearance to |
|
| horizontal distance of (24"/60cm) from the centerline of the terminal (min. |
| air inlet to any other appliance *(12"/30cm) |
|
| 18"/46cm) check with local code. | L= | Clearance to a mechanical air supply inlet *(min. 72"/1.8m) |
|
E= | Clearance to unventilated soffit (min. 12"/30cm) | M= | **Clearance above paved sidewalk or a paved driveway located on public |
|
F= | Clearance to outside corner: with AstroCap Termination Cap (min. 6"/15cm), |
| property *(min. 84"/2.1m) |
|
| with | N= | Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)*** |
|
G= | Clearance to inside corner: with AstroCap Termination Cap (min. 6"/15cm), |
|
|
|
Note: * As specified in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.
**A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
INSTALLATION