How to Test Run the Air Conditioner
After turning on power to the air conditioner, use the remote controller and follow the steps below to conduct the test run.
(1)Set the remote controller in Test Run mode. (Fig. 59a)
a)Press and hold the ION button.
b)Then press and hold the 1HR TIMER button.
c)At the same time, press the ACL (reset) button once. Use a pointed object such as the tip of a pen to press the ACL button.
•After a few seconds, “ ” appears and
(Fig. 59b)
d)Release the 1HR TIMER button.
e)Release the ION button.
(2)Start Cooling mode test run by pressing the ON/OFF operation button of the remote controller. (Fig. 59a)
•This starts the fan producing uncooled forced air with the 4 indicator lamps (OPERATION lamp, TIMER lamp, QUIET lamp, and ION lamp) on the main unit blinking. (Fig. 59c)
•After 3 minutes, the system shifts into cooling opera- tion, and cool air will start to be felt. Cool mode test run is unaffected by the room temperature.
(3)Press the ON/OFF operation button of the remote con- troller again to stop the test run. (Fig. 59a)
(4)Finally press the ACL (reset) button of the remote con- troller to release it from Test Run mode to return to nor- mal mode. (Fig. 59a)
•“ ” and
NOTE
Troubleshooting:
In the event that the green “Operation Light” is blinking upon powering up the system, an error condition exists. In this case, refer to the
inside of the front cover.
IMPORTANT
After the test run is completed, be sure to press the ACL (reset) button to return to normal mode. The air conditioner will not operate correctly if this is not done.
| ON/OFF | |
ION | operation | |
button | ||
button | ||
|
1HR.
TIMER button
A | ACL | |
(Reset) | ||
| ||
| button |
Fig. 59a
Fig. 59b
OPERATION lamp
TIMER lamp
QUIET lamp
ION lamp
Fig. 59c