Sanyo CH1271 Unit Specifications, Voltage Rating, Performance, Electrical, Features, Weight

Models: CH0971 CH1271

1 104
Download 104 pages 60.02 Kb
Page 6
Image 6

2. SPECIFICATIONS

2-1. Unit Specifications

Indoor Unit

KHS0971

 

 

 

 

 

 

 

 

Outdoor Unit

CH0971

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Rating

 

 

 

 

 

 

115V Single-Phase 60Hz

Performance

 

 

 

 

 

 

 

 

 

Cooling

 

 

Heating

 

Total Capacity

 

 

 

 

BTU/h

9,000

( 3,000 to 9,000 )

 

12,200

( 3,000 to 12,200 )

 

 

 

 

 

 

 

kW

2.65

( 0.9 to 2.65 )

 

3.6

( 0.9 to 3.6 )

 

Sensible Capacity

 

 

 

 

BTU/h

 

7,650

 

 

-

 

Latent Capacity

 

 

 

 

BTU/h

 

1,350

 

 

-

 

Air Circulation (High)

 

 

ft3/min (m3/h)

 

282 (480)

 

 

312 (530)

 

 

Moisture Removal (High)

 

 

Pints/h

 

3.4

 

 

-

 

 

Available Voltage Range

 

 

V

 

104 to 126

 

Rating

Running Amperes

 

 

 

 

A

7.6

( 2.5 to 7.6 )

 

10.3

( 2.6 to 10.3 )

Power Input

 

 

 

 

 

W

720

( 250 to 720 )

 

995

( 250 to 995 )

Power Factor

 

 

 

 

%

 

83

 

 

84

EER

 

 

 

 

 

BTU/h/W

 

12.5

 

 

-

Electrical

 

 

 

 

 

 

 

 

COP

 

 

 

 

 

W/W

 

-

 

 

3.62

SEER

 

 

 

 

 

BTU/Wh

 

16

 

 

-

HSPF

 

 

 

 

 

BTU/Wh

 

-

 

 

8.5

 

 

Compressor Locked Rotor Amperes

 

 

A

 

 

20

 

 

 

Fuse or Circuit Breaker Capacity

 

 

A

 

 

20

 

 

 

Controls / Temperature Control

 

 

 

 

Microprocessor / I.C. Thermister

 

 

Control Unit

 

 

 

 

 

 

 

Wireless Remote Control Unit

 

 

Timer

 

 

 

 

 

 

 

24-Hour ON or OFF Timer, 1-Hour OFF Timer

 

 

Fan Speeds

 

 

Indoor / Outdoor

 

Auto and 3 steps / Auto (Hi, Me, Lo)

 

 

Airflow Direction (Indoor)

 

 

Horizontal

 

Manual

 

 

 

 

 

 

 

 

 

Vertical

 

Auto

 

Features

Air Filter

 

 

 

 

 

 

 

Washable, Anti-Mold

Compressor

 

 

 

 

 

 

 

DC Rotary (Inverter)

Refrigerant / Amount charged at shipment

 

 

Ibs (g)

 

R410A / 2.09 (950)

Refrigerant Control

 

 

 

 

 

 

Electric Expansion Valve

 

 

 

 

 

 

 

 

 

 

Operation Sound

 

Indoor : Hi/Me/Lo/Qt*

dB-A

 

34 / 31 / 28 / 23

 

34 / 31 / 28 / 23

 

 

(*Qt = Quiet mode)

 

Outdoor : Hi

 

 

dB-A

 

46

 

 

47

 

 

Refrigerant Tubing Connections

 

 

 

 

Flare Type

 

 

 

Max. allowable tubing length at shipment

 

 

ft (m)

 

25 (7.5)

 

 

 

Refrigerant

 

 

Narrow tube

 

 

inch (mm)

 

1/4 (6.35)

 

 

 

Tube Diameter

 

Wide tube

 

 

inch (mm)

 

3/8 (9.52)

 

 

 

Refrigerant Tube Kit / Accessories

 

 

 

 

Optional / Air Clean Filter

Weight

 

 

 

 

 

 

 

 

Indoor Unit

 

 

Outdoor Unit

Unit Dimensions

 

 

 

 

inch

11-7/32 32-15/32 7-7/16

 

21-9/16 28-11/32 10-7/16

Height Width

Depth

 

 

(mm)

(285 825 189)

 

(548 720 265)

&

 

 

 

 

 

Package Dimensions

 

 

 

 

inch

10-1/32 35-7/16 13-25/32

 

23-5/8 33-11/16 14-1/4

Dimensions

 

 

 

 

 

Height Width Depth

 

 

(mm)

(255 900 350)

 

(600 856 362)

Weight

 

 

Net

 

 

Ibs (kg)

 

19.8 (9.0)

 

 

75.0 (34.0)

 

 

 

Shipping

 

 

Ibs (kg)

 

24.3 (11.0)

 

 

81.6 (37.0)

Shipping Volume

 

 

 

 

cu.ft (m3)

 

2.82 (0.08)

 

 

6.35 (0.18)

 

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Remarks: Rating conditions are:

 

 

 

Cooling: Indoor air temperature

80°F D.B. / 67°F W.B.

Heating: Indoor air temperature

70°F D.B.

Outdoor air temperature

95°F D.B. / 75°F W.B.

Outdoor air temperature

47°F D.B. / 43°F W.B.

6

Page 6
Image 6
Sanyo CH1271, CH0971 Unit Specifications, Voltage Rating, Performance, Electrical, Features, Weight, Dimensions