Sanyo CH0971, CH1271 Control PCB, Compressor, Fan Motor, Heat Exchanger Coil, External Finish

Models: CH0971 CH1271

1 104
Download 104 pages 60.02 Kb
Page 11
Image 11
Manual background

Outdoor Unit CH1271

Control PCB

Part No.

Controls

Control Circuit Fuse

Compressor

CB-CH1271

Microprocessor

125V 25A

 

Type

 

 

DC Rotary (Inverter)

 

Compressor Model / Nominal Output

 

 

G4C090LU1ER / 900W

 

Compressor Oil ... Amount

Pints (cc)

FV50S ... 0.68 (320)

 

Coil Resistance (Ambient Temp. 68 °F (20 °C)) Ohm

U - V : 0.81

 

 

 

 

 

V - W : 0.81

 

 

 

 

 

W - U : 0.81

 

Safety Device

 

 

Yes

 

 

CT (Peak current cut-off control)

 

 

Compressor Discharge Temp. Control

Yes

 

 

Operation cut-off control in abnormal ambient Temp.

Yes

 

 

Overload Relay

 

Model

CS-7L115

 

 

 

Operation Temp.

Open : 239 °F (115 °C), Close : 203 °F (95 °C)

 

Run Capacitor

 

Micro F

-

 

 

 

 

VAC

-

 

Crankcase Heater

 

 

115V 20W

Fan

Type

 

Q'ty ... Dia.

inch (mm)

Propeller

1 ... D15-3/4 (D400)

Fan Motor

 

 

 

Type

 

DC Motor

 

Model ... Q'ty

 

DAJ12-55J71-CU ... 1

 

No. of Poles

 

8

 

Rough Measure RPM (Cool / Heat)

 

750 / 750

 

Nominal Output

W

50

 

Coil Resistance

Ohm

RED - WHT : 77.5

 

(Ambient Temp. 68 °F (20 °C))

 

WHT - BLU : 77.5

 

 

 

 

BLU - RED : 77.5

 

Safety Device

 

 

 

 

Type

 

Internal Controller

 

 

Over- Current Protection

 

Yes

 

Run Capacitor

Micro F

-

 

 

 

VAC

-

 

 

 

 

 

Heat Exchanger Coil

 

 

 

Coil

 

Aluminum Plate Fin / Copper Tube

 

Rows

 

2

 

Fins per inch

 

18.1

 

Face Area

ft2 (m2)

3.95 (0.367)

External Finish

Acrylic baked-on enamel finish

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

11

Page 11
Image 11
Sanyo CH0971, CH1271 service manual Control PCB, Compressor, Fan Motor, Heat Exchanger Coil, External Finish