7-1-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 4)
damp, humid or uneven locations.
DO:
NO
Hot air
Outdoor unit
Exhaust fan
Heat source
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/exhaust and possible maintenance. (Fig. 5a)
provide a solid base (level concrete pad, concrete block, 10 ⋅ 40 cm beams or equal), a minimum of 10 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 5b)
Install cushion rubber under unit’s feet to reduce vibration and noise. (Fig. 5c)
use lug bolts or equal to bolt down unit, reducing vibration and noise.
Install in a location where no antenna of a television or radio exists within 3 meters.
Air intake | Min. 5 cm | Valve | |
|
|
| side |
|
|
| Min. |
|
|
| 25 cm |
Min. | Air discharge | Min. | ||
5 cm | ||||
|
| 20 cm | ||
|
|
|
Fig. 5a
Anchor bolts (4 pcs.)
Air intake | Min. 10 cm |
Concrete or equal
About |
| 10 | cm |
40 | About |
| |
|
| ||
| cm |
| |
|
|
|
Fig. 5b
Obstacle above
Airdischarge |
|
|
| Obstacle | |
|
|
| Min. | Min. | |
|
|
| 2 m | 2 m | |
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ground
Min. 5 cm
Air intake
Cushion rubber (Locally purchased)
Fig. 5c