Fig. 4

7-1-2. Outdoor Unit

AVOID:

heat sources, exhaust fans, etc. (Fig. 4)

damp, humid or uneven locations.

DO:

NO

Hot air

Outdoor unit

Exhaust fan

Heat source

choose a place as cool as possible.

choose a place that is well ventilated.

allow enough room around the unit for air intake/exhaust and possible maintenance. (Fig. 5a)

provide a solid base (level concrete pad, concrete block, 10 40 cm beams or equal), a minimum of 10 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 5b)

Install cushion rubber under unit’s feet to reduce vibration and noise. (Fig. 5c)

use lug bolts or equal to bolt down unit, reducing vibration and noise.

Install in a location where no antenna of a television or radio exists within 3 meters.

Air intake

Min. 5 cm

Valve

 

 

 

side

 

 

 

Min.

 

 

 

25 cm

Min.

Air discharge

Min.

5 cm

 

 

20 cm

 

 

 

Fig. 5a

Anchor bolts (4 pcs.)

Air intake

Min. 10 cm

Concrete or equal

About

 

10

cm

40

About

 

 

 

 

cm

 

 

 

 

Fig. 5b

Obstacle above

Airdischarge

 

 

 

Obstacle

 

 

 

Min.

Min.

 

 

 

2 m

2 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ground

Min. 5 cm

Air intake

Cushion rubber (Locally purchased)

Fig. 5c

33

Page 33
Image 33