8. FUNCTIONS

8. FUNCTIONS

8-1. Room Temperature Control

(1) Cooling

8-1. Room Temperature Control Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the indoor unit.

NOTE Some informations except for the room temperature are transmitted every 5 minutes by the remote control unit to the controller in the indoor unit.

 

 

 

Thermo.

Thermo.

Thermo.

Thermo.

Thermo.

 

 

 

OFF

ON

OFF

ON

OFF

 

T+1°C

 

 

 

 

 

 

Set temp.

T °C

 

 

 

 

 

 

 

 

 

 

 

 

 

Room temp.

Compressor

ON

OFF

ON

OFF

ON

OFF

Outdoor fan

ON

OFF

ON

OFF

ON

OFF

Manual background Once the compressor starts, it keeps running for 5 minutes.

Manual background Once the compressor stops, it will not start running again for 3 minutes.

Manual background Thermo. ON : When room temperature rises 1°C above the set temperature T°C, the compressor turns ON.

Manual background Thermo. OFF : When the room temperature falls below the set temperature T°C, the compressor turns OFF.