8-2. Dry Operation (Dehumidification)

8-2. Dry Operation (Dehumidification)

< Cooling operation > Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of turning ON and OFF automatically as shown in the chart below according to the room temperature.

T°C

T-1°C

Room temp. 15°C

 

T : Set temp.

 

When room temp.

 

 

 

 

 

 

goes up

 

< Cooling operation >

 

 

 

 

 

The air conditioner operates in cooling mode.

 

 

 

T+2°C

 

 

 

 

 

 

 

< Dry A zone >

 

 

 

 

 

 

 

 

 

 

 

Compressor :

Continuous operation

 

 

 

T+1°C

 

 

 

FMI (indoor fan) : Indoor fan operates with rhythm airflow.

 

 

 

 

 

 

T-1°C

 

< Dry B zone >

 

 

 

 

 

 

 

 

 

 

Compressor : Intermittent operation

(ON for 3 minutes and OFF for 9 minutes) FMI (indoor fan) : Indoor fan operates with rhythm airflow.

Room temp. 15°C

<Monitor zone >

Both the indoor and outdoor units stop.

When room temp.

goes down

NOTE

< Dry A zone > Intermittent ventilation occurs by switching the indoor fan speed between L and LL.

< Dry B zone > DRY operation does not occur when the room temperature is 15°C or less, which is the monitor zone.

<Monitor zone > When the compressor stops, the indoor fan stops as well.

40

Page 40
Image 40
Sanyo SAP-K77RAX service manual Dry Operation Dehumidification, Cooling operation, Dry A zone, Dry B zone, Monitor zone