8-3. Freeze Prevention (Cooling and Dry)

This function prevents freezing of the indoor heat exchange coil.

When the temperature of the indoor heat exchange coil falls below 2 °C for 2 minutes, the control circuit stops the outdoor fan and compressor (The compressor stops 3 seconds after the outdoor fan stopped). During this period, Indoor fan operates in LL. The outdoor fan does not start again until the temperature rises above 6°C. (The compressor starts 2 seconds after the outdoor fan started.)

6°C

Indoor heat

exch. coil

temp.

2°C

Outdoor fan

Compressor

At least approx. 2 min.

3 sec.

 

 

 

 

 

 

 

 

 

 

ON

 

 

OFF

 

 

ON

 

 

 

 

 

 

 

 

 

 

2 sec.

 

 

 

 

 

 

 

 

 

 

ON

 

 

OFF

 

 

ON

 

 

 

 

 

 

 

 

 

 

Indoor fan

Set Speed

LL

Set Speed

41