DiagnosticTools
70
6.13 Option 6:NodeErrorStatistics
Figure27 NodeErrorStatistics
MODBUS PLUS NETWORK STATUS version 2.10
Node Error Counters, Press SPACE to clear.
Adapter: 1
Success: 182
Failure: 0
Information from node 5 (05.00.00.00.00)
0 Pre-transmit deferral error counter
0 Receive buffer DMA overrun error counter
0 Repeated Command received error counter
0 No Try (nonexistent station) error counter
0 Cable A framing error
0 Cable B framing error
0 Receiver CRC error counter
0 Bad packet length error counter
0 Transmit buffer DMA underrun error counter
0 Bad internal packet-length error counter
0 Bad MAC-function-code error counter
0 Communication failed error counter
244 Good receive packet success counter
0 No response received error counter
0 Exception response received error counter
0 Unexpected path error counter
0 Unexpected response error counter
0 Forgotten transaction error counter
Thisoption continuouslyqueriesthe specified node foralistofitserrorstatistics
and displays the list. Asthe testruns, the countsinthe display can be reset to
zerosbypressing the Space bar.
If you arerunning the utilityonasingle-cablenetwork,one of the framing error
counterswill be incrementing continuouslydue tothe open connection on the
monitoring devicesothercableconnector.Forexample,ifyoursinglecableis
connected tothe CableAconnector,the CableBframing errorcounterwill
incrementcontinuously. Insuchcasesyou can disregardthe counter.
The option runs continuouslyand displays a pass countuntil you terminateitby
pressing Escape.