External Power Supply

48049-136-05

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

Rev. 01, 07/2012

Section 1—General Information

 

 

The following will be powered and functional with external power:

All of the above functions which are functional without external power.

Ammeter and bar graph displays are functional with or without current flowing through the circuit breaker. With current flow between 0 and 20% of sensor value, the ammeter may not be accurate.

Trip settings and max. current readings can be accessed on the display be pressing the navigation buttons with or without current flowing through the circuit breaker.

Ground-fault push-to-trip button works for testing ground fault with or without current flowing through the circuit breaker.

Optional Modbus communications are functional, using a separate 24 Vdc power supply for the circuit breaker communications module. This separate 24 Vdc power supply is required to maintain the isolation between the trip unit and communications.

The ground-fault push-to-trip is also functional if a Hand-Held Test Kit or

Full-Function Test Kit is powering the trip unit.

External Power Supply

The trip unit display can be powered by a 24 Vdc external power supply.

ENGLISH

HAZARD OF SHOCK, ARC FLASH OR EQUIPMENT DAMAGE CAUTION

HAZARD OF SHOCK, ARC FLASH OR EQUIPMENT DAMAGE

Trip unit and communication module must use separate power supplies.

Failure to follow this instruction can result in personal injury or equipment damage.

Table 7:

Power Supply Specifications

 

 

 

 

 

 

 

 

 

 

Function

 

Specification

 

 

 

 

 

 

 

 

 

Power for Trip Unit Alone

24 Vdc, 50 mA

 

 

 

 

 

 

 

 

 

Minimum Input-to-Output Isolation

2400 V

 

 

 

 

 

 

 

 

 

Output (Including Max. 1% Ripple)

±5%

 

 

 

 

 

 

 

 

 

 

 

 

Dielectric Withstand (Input/Output)

3 kV rms

 

 

 

 

 

 

 

 

 

 

 

 

Connections UC3

 

 

Connections

 

F1 (-)

 

 

 

 

24 Vdc

 

 

F2 (+)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply is used for graphic scree display when the circuit breaker is open or not carrying current.