Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

48049-136-05

Section 3—Operation

Rev. 01, 07/2012

 

 

ENGLISH

Section 3—Operation

Switch Setting Adjustment

1.Open switch cover (A).

2.Adjust the appropriate switches (B) to desired values.

3.Replace switch cover. Use wire seal MICROTUSEAL (C, not provided), if necessary, to provide tamper evidence.

Examples

Circuit breaker is rated 2000 A.

Figure 23: Adjust Switch Settings

06133205

06133206

06133207

A

C

 

 

B

Figure 24: Circuit Breaker Rating

06133208

In 2000 A

Micrologic 2.0A Trip Unit

Figure 25: Set Pickup Levels

1. Set pickup levels.

06134251

long time

Ir

.8

alarm

.7

.9

 

.6

 

.95

 

.5

 

.98

 

.4 x In 1

 

instantaneous

 

Isd

4

 

 

3

5

 

2.5

 

6

 

2

 

8

 

1.5 x Ir

10

 

setting

In = 2000 A

Ir = 0.7 x In = 1400 A

Isd = 2 x Ir = 2800 A

06134245

t

0 Ir

Isd

20-EN

© 1999–2012 Schneider Electric All Rights Reserved

Page 22
Image 22