Section 5—Adjustable Rating Plug Replacement

 

 

Section 5—Adjustable Rating Plug Replacement

NOTE: To select correct replacement rating plug, see the product catalog.

NOTE: If adjustable rating plug is removed, the circuit breaker will default to a long-time pickup rating of 0.4 x In and a long-time delay at whatever setting was selected before the rating plug was removed.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E or CSA Z462.

This equipment must be installed and serviced only by qualified electrical personnel.

Turn off all power supplying this equipment before working on or inside equipment. Follow instructions shipped with circuit breaker to disconnect and reconnect circuit breaker.

Replace all devices, doors and covers before returning equipment to service.

Failure to follow this instruction will result in death or serious injury.

ENGLISH

Rating Plug Removal

1. Open circuit breaker contacts:

Figure 48: Remove Adjustable Rating Plug

B

C

 

— For Masterpact NT and NW circuit

 

breakers, press the “Push to open”

 

button on the circuit breaker.

 

— For other circuit breakers, move handle

 

to the off (O) position.

2.

Open switch cover (A).

3.

Unscrew adjustable rating plug mounting

 

screw (B).

4.

Remove adjustable rating plug (C).

06133205

06133221

A

long time

tr

4

8

 

12

Ir .7

.8

.9

(s)

 

 

16

 

2

 

 

 

20

.6

 

.95

1

 

 

 

24

 

.98

 

.5

@

6 Ir

.5

x In

1

 

 

 

 

.4

 

 

 

 

 

 

short time

tsd

.4

.4

.3

Isd

4

56

.3

 

 

.2

3

 

 

 

.1

2.5

 

8

.2.1

 

t

0

2

 

10

on

I

 

1.5 x Ir

 

 

 

delay

 

setting

 

 

 

 

 

alarm

 

instantan

eous

I i

4

5

2.5

3

6

 

8

2

 

10

1.5 x In

 

06133222

 

 

 

 

 

 

 

instantane

ous

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I i

4

5

 

 

 

 

 

 

 

short tim

 

.4

.3

3

 

6

 

 

 

 

 

 

 

2.5

 

 

 

 

 

 

 

Isd

4

 

.3

 

 

.2

 

8

 

 

 

 

 

alarm

5

 

 

.1

2

 

10

 

 

 

 

 

 

3

 

6

.2.1

 

 

1.5

x In

long time

(s)tr

 

8

1216

2.5

 

8

2

t

0

 

 

4

2

 

10

on

I

 

 

 

 

Ir

.8

.9

2

 

 

20

1.5

x Ir

delay

 

 

 

.7

 

.95

 

 

 

 

 

 

 

 

 

 

 

.6

 

.98

1

.5

 

24

setting

 

 

 

 

 

 

 

.5

 

1

 

@ 6 Ir

 

 

 

 

 

 

 

 

 

 

.4

x In

 

 

 

 

 

New Rating Plug Installation

1.Inspect mounting area for debris and contamination.

2.Gently push in new adjustable rating plug

(A).

3.Tighten adjustable rating plug mounting screw (B).

4.Set the switches on the trip unit (see Section 3 —Operation).

5.Close switch cover (C).

Figure 49: Install New Adjustable Rating Plug

06133223

A

06134244

B

 

 

 

 

 

 

 

alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

long time

tr

4

8

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ir

 

.8

.9

(s)

 

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.7

 

2

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.6

 

.95

1

 

 

 

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.98

 

.5

@

6 Ir

instantan

eous

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.5

x In

1

 

 

 

 

 

 

 

 

 

 

instantaneous

 

 

 

 

 

 

 

.4

 

 

 

 

 

 

I i

4

5

 

 

 

 

 

 

 

 

 

 

 

 

 

short time

tsd

.4

.4

.3.2

2.53

 

 

68

 

 

t time

 

 

I i

4

5

 

 

 

 

 

 

Isd

4

5

.3

 

 

.1

2

 

10

shor

 

tsd

2

2.5

 

8

 

 

 

 

 

 

2.5

 

8

.2.1

I

t

0

 

x In

 

 

Isd

4

56

.3

1

2

 

10

 

 

 

 

 

 

alarm

2

 

10

on

 

 

 

 

 

3

 

1.5 x In

 

 

 

 

 

 

 

1.5

 

delay

 

 

 

 

 

2.5

 

 

.2

0

 

long time

tr

 

8

12

 

x Irg

 

 

 

 

 

 

 

 

 

2

 

8

.1

I2t

 

 

test

Ir

.8

.9

(s)

4

 

16

settin

 

 

 

 

 

 

 

 

 

 

1.5

 

10

on

delay

 

 

 

.7

 

.95

2

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

x Ir

 

 

 

 

 

.6

 

.98

1

 

 

24

 

 

 

 

 

 

 

 

 

 

 

 

setting

 

 

 

 

 

.5

 

1

 

.5

@ 6 Ir

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.4

x In

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

© 1999–2012 Schneider Electric All Rights Reserved

33-EN

Page 35
Image 35
Schneider Electric 5.0A, 3.0A, 2.0A Adjustable Rating Plug Replacement, Rating Plug Removal, New Rating Plug Installation