Schneider Electric and 6.0A, 3.0A, 2.0A, 5.0A manual Instantaneous Protection Switches, English

Models: 3.0A and 6.0A

1 40
Download 40 pages 1.37 Kb
Page 14
Image 14
Instantaneous Protection

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

48049-136-05

Section 1—General Information

Rev. 01, 07/2012

 

 

Instantaneous Protection

Figure 9: Instantaneous Protection Switches

ENGLISH

Instantaneous protection protects equipment against short circuits with no intentional time delay.

Instantaneous protection (Ii) (A) is standard

on the 3.0A, 5.0A and 6.0A trip units.

Instantaneous protection on 2.0A trip units is

achieved by using short-time protection (Isd)

with the short-time delay factory set to 0

(zero).

Instantaneous protection on the 3.0A, 5.0A

and 6.0A trip units is based on the circuit

Micrologic 2.0A Trip Unit

06134243

.6

 

 

.95

2

 

16

 

 

 

 

 

 

 

long time

tr

 

 

alarm

 

 

Ir

.8

 

4 8

 

 

 

.7

.9

(s)

12

 

 

 

 

 

 

.5

 

 

.98

1

 

20

 

 

 

 

 

 

 

.4 x In 1

 

.5 @ 6 Ir24

 

 

 

 

 

 

 

instantaneous

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Isd

4

 

 

 

 

 

 

 

 

 

 

3

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

 

 

6

 

 

 

 

 

 

 

 

A

2

 

 

8

 

 

 

 

 

 

 

 

1.5 x Ir 10

 

 

 

 

 

 

 

 

 

setting

 

 

 

 

 

 

 

 

 

Micrologic 3.0A Trip Unit

06133203

.6

 

 

.95

2

 

16

 

 

 

 

 

 

 

long time

tr

 

 

alarm

 

 

Ir

.8 .9

4 8

 

 

 

.7

(s)

12

 

 

 

 

 

 

.5

 

 

.98

1

 

20

 

 

 

 

 

 

 

.4 x In 1

 

.5 @ 6 Ir24

 

 

 

 

 

 

 

instantaneous

 

 

 

 

 

 

 

 

 

Ii

5

 

 

 

 

 

 

 

 

 

 

4

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

8

 

 

 

 

 

 

 

 

 

2

 

 

10

 

 

 

 

 

 

 

 

A

1.5

x In

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting

 

 

 

 

 

 

 

 

breaker sensor rating (In).

Micrologic 5.0A Trip Unit

Micrologic 6.0A Trip Unit

Instantaneous protection on the 2.0A trip unit

is based on the long-time pickup setting (Ir).

Circuit breaker open command is issued as

soon as threshold current is exceeded.

Instantaneous protection uses peak current

measurement.

When instantaneous protection switch is set

to off, the instantaneous protection is

disabled.

06133204

 

 

long time

 

 

 

 

 

 

 

 

 

 

Ir

.8 .9

 

 

 

tr

 

 

8

 

 

 

.7

 

 

 

(s)

4

12

 

 

.6

 

 

.95

 

2

 

 

 

16

 

 

.5

 

 

.98

 

1

 

 

 

20

 

 

.4 x In 1

 

 

.5 @ 6 Ir24

 

 

 

 

 

 

 

short time

 

 

 

 

 

 

 

 

 

Isd

4

 

 

 

 

tsd

 

.4

.3

 

3

5

 

 

 

(s)

.4

 

 

 

 

.3

 

 

.2

 

2.5

 

 

6

 

 

 

 

 

2

 

 

8

 

 

.2

 

 

.1

 

1.5

 

10

 

 

 

 

.1

2

0

 

 

 

 

x Ir

 

 

 

 

on

I t

off

 

 

setting

 

 

 

delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

alarm

instantaneous

I i

8

6 Figure 9: Instantaneous Protection Switches 10

4achieved by using short-time protection (Isd) 12

3Manual backgroundManual backgroundManual background15

2off

x In

06133351

A

long time

 

 

 

 

 

 

Ir

.8

 

tr

 

8

 

alarm

 

.7

.9

(s) 4

12

 

 

.6

 

.95

2

 

 

16

 

 

.5

 

.98

1

 

 

20

 

 

.4 x In 1

.5 @ 6 Ir24

 

 

short time

tsd

 

 

 

instantaneous

Isd

4

 

.4

.4 .3

I i

 

3

5

(s)

5 8

10

2.5

 

6

.3

 

 

.2

4

12

2

 

8

.2

 

 

.1

3

 

1.5 x Ir

10

.1

I2t

0

2 x Inoff

on

off

setting

 

delay

 

 

test

Ig

 

 

tg

 

 

 

 

E

 

.4

.4 .3

 

 

D

F

(s)

 

 

C

 

G

.3

 

 

.2

 

 

B

 

H

.2

 

 

.1

 

 

A

 

J

.1

I2t

0

 

 

 

on

off

 

 

ground fault

A

Table 3:

Micrologic Instantaneous Values

 

 

 

 

Setting

 

Interruption Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0A

Isd (= Ir x..)

1.5

2

2.5

3

4

5

6

8

10

 

 

 

 

 

 

 

 

 

 

 

 

3.0A

Ii (= In x..)

 

1.5

2

3

4

5

6

8

10

12

 

 

 

 

 

 

 

 

 

 

 

 

5.0A

Ii (= In x..)

 

2

3

4

6

8

10

12

15

off

 

 

 

 

 

 

 

 

 

 

 

 

6.0A

Ii (= In x..)

 

2

3

4

6

8

10

12

15

off

 

 

 

 

 

 

 

 

 

 

 

 

Ii = UL and ANSI instantaneous

Isd = IEC instantaneous (short-time with zero delay)

In = sensor rating

Ir = long-time pickup

12-EN