Register List (continued)

48049-136-05

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

Rev. 01, 07/2012

Appendix A—Register List

 

 

Table 10:

Register List (continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

SMS Topic Name

User Description

Number of

Register*

Module*

Units

Scale/Bitmask

Registers*

 

 

 

 

 

 

 

TU_BATT_PCT

 

Trip Unit % Battery

1

8843

PM

%

Unity

TU_SN

 

Trip Unit Serial Number

4

8700

PM

 

ASCII text

 

 

 

 

 

 

 

 

TUCommStatus

 

Trip Unit Internal Comms Status

1

552

BCM

 

Bit 11; ON = not responding, OFF = OK

*For register entries that are not listed, please refer to the Micrologic device type register list. Contact your local sales office.

BCM = Circuit breaker communication module. CCM = Cradle communication module. PM = Trip unit protection module.

3-register date/time format: register 1: month (byte 1) = 1–12, day (byte 2) = 1–31; register 2: year (byte 1) = 0–199 (add to 1900 to determine the actual year), hour

(byte 2) = 0–23; register 3: minutes (byte 1) = 0–59, seconds (byte 2) = 0–59. Note: Bits 14 and 15 of the month/day register must be masked.

**Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = –9,999 to +9,999). Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. Range is zero to 9,999,999,999,999,999.