Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units | |
Rev. 01, 07/2012 | Section |
|
|
2. Set time delay. | Figure 26: | Set Time Delay | ||||||||||
| 06133211 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| long time | (s) | 4 12 | alarm |
| |||||
|
|
|
|
| tr | 8 |
| |||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| 2 | 16 |
|
|
|
|
|
| ||
|
|
| 1 | 20 |
|
|
|
|
|
| ||
|
|
|
|
|
| .5 @ 6 Ir24 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
tr = 1 s (at 6 x Ir)
t |
|
06133212 |
|
1 s | tr |
0 | 6 |
| x Ir |
I
ENGLISH
Micrologic 3.0A Trip Unit
1. Set pickup levels.
Figure 27: Set Pickup Levels | |||
06133209 | long time | ||
Ir | .8 | alarm | |
.7 | .9 | ||
| .6 |
| .95 |
| .5 |
| .98 |
| .4 x In 1 | ||
| instantaneous | ||
| Ii | 5 |
|
| 4 | 6 | |
| 3 |
| 8 |
| 2 |
| 10 |
| 1.5 | x In | 12 |
|
|
| |
| setting |
In = 2000 A
Ir = 0.7 x In = 1400 A
Ii = 3 x In = 6000 A
06133210 | t | |
Ir | ||
|
Ii
0 | 6000 A |
1400A |
I
2. Set time delay.
Figure 28: Set Time Delay
06133211 |
|
| long time | (s) | 4 |
| 12 | alarm | ||
|
|
| tr |
| 8 |
| ||||
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
216
1 20
.5 @ 6 Ir24
tr = 1 s (at 6 x Ir)
t |
|
06133212 |
|
1 s | tr |
0 | 6 |
| x Ir |
I
Micrologic 5.0A Trip Unit
Figure 29: Set Pickup Levels
1. Set pickup levels.
06133213 | long time |
|
|
|
| ||
Ir | .8 |
|
| alarm |
| ||
.7 | .9 |
|
|
|
| ||
| .6 |
| .95 |
|
|
|
|
| .5 |
| .98 |
|
|
|
|
| .4 | x In 1 |
|
|
|
| |
| short time |
| instantaneous | ||||
| Isd | 4 | 5 |
| I i | 8 | 10 |
| 3 |
| 6 | ||||
|
|
|
| ||||
| 2.5 |
| 6 |
| 4 |
| 12 |
| 2 |
| 8 |
| 3 |
| 15 |
| 1.5 | x Ir | 10 | off | 2 |
| off |
|
|
|
| x In | |||
| setting |
|
|
|
|
In = 2000 A
Ir = 0.7 x In = 1400 A
Ii = 6 x In = 12000 A
Isd = 2 x Ir = 2800 A
t | Ir |
|
06133214 |
| |
|
| |
|
| Isd |
|
| Ii |
0 |
| 12000 A |
1400A | 2800 A |
I
© |
|