Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

Rev. 01, 07/2012

Section 3—Operation

 

 

Zone-Selective Interlocking (ZSI)

Table 8:

ZSI Combinations

The number of devices which can be interlocked are shown in Table 8.

 

Upstream Device

UnitsTrip#.0xMicrologic

UnitsTripBSeriesMicrologicDSquare

RelayFault-Ground100-GCDSquare ProtectionEquipmentfor

RelayFault-Ground200-GCDSquarefor ProtectionEquipment

UnitsTripSTR58GerinMerlin

TripUSRCMandUSRCPioneerFederalUnits

 

 

 

 

 

 

 

 

(receives input from RIM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Downstream Device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(sends output to RIM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Micrologic #.0x Trip Units

15

R

R

15

15

R

 

 

 

 

 

 

 

 

 

 

Square D Micrologic Series B Trip Units

R

26

R

R

R

15

 

 

 

 

 

 

 

 

 

 

Square D GC-100 Ground-Fault Relay

R

R

7

R

R

R

for Equipment Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Square D GC-200 Ground-Fault Relay

15

R

R

15

15

R

for Equipment Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Merlin Gerin STR58 Trip Units

15

R

R

15

15

R

 

 

 

 

 

 

 

 

 

 

Merlin Gerin STR53 Trip Units

15

R

R

15

15

R

 

 

 

 

 

 

 

 

 

 

Federal Pioneer USRC and USRCM Trip

R

15

R

R

R

15

Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Square D Add-On Ground Fault Module

R

5

R

R

R

R

for Equipment Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R—RIM module is required to restrain any devices.

Numerical References—Maximum number of upstream circuit breakers which can be restrained without requiring a RIM Module.

ENGLISH

Circuit breaker terminals are shipped with terminals Z3, Z4 and Z5 jumpered to self- restrain the short-time and ground-fault functions. Remove the jumpers when activating zone-selective interlocking.

Figure 33: Jumpered Terminals

UC1

Z5 M1

Z3 Z4

Z1 Z2

Auxiliary Connections

© 1999–2012 Schneider Electric All Rights Reserved

23-EN

Page 25
Image 25
Schneider Electric 2.0A, 3.0A, and 6.0A, 5.0A manual Zone-Selective Interlocking ZSI, ZSI Combinations, Units, 23-EN